Nexans AIN Indoor MV Slip-On Cold Shrink Terminations (Single Core | 42kV)
Product overview
Nexans AIN Indoor MV Slip-On Cold Shrink Terminations (Single Core | 42kV)
Nexans AIN Indoor MV Slip-On Cold Shrink Terminations (Single Core | 42kV) are reliable, high-performance indoor terminations for polymeric insulated MV cables with extruded or bonded conductive screens. These Nexans AIN Terminations deliver long-term electrical performance in controlled indoor environments. The range includes AIN 10, AIN 20, AIN 30 and AIN 36, covering voltages up to 42kV. Slip-on silicone housings make installation fast and easy without heat or special tools, and a few sizes cover most cable cross-sections. Compatible with three-core, copper wire screened or copper tape screened and armoured cables, this AIN Single Core system is a versatile, dependable indoor solution.
Part Numbers: AIN 10, AIN 20, AIN 30, AIN 36.
Nexans AIN – Kit Contents
- x3 termination housings
- x3 mechanical or compression cable lugs for the conductor
- x3 mechanical or compression screen wire cable lugs
- Installation instructions
- Silicone grease
- Assembly incidentals
AIN Indoor MV Terminations – Features
- Voltage class: Up to 42kV
- Application: Indoor use on polymeric insulated MV cables
- Type: Slip-On Cold Shrink Termination
- Material: High-quality silicone rubber
- Standards: CENELEC HD 629.1
- Quick installation without heat or special tools
- Suitable for three-core, copper wire screened or copper tape screened and armoured cables
Order Information
Below, you can easily select the Nexans AIN Indoor MV Slip-On Cold Shrink Terminations for each cable voltage:
MAX VOLTAGE 6-10 kV
| Part No | Section | Core Length |
| 3 x AIN 10 Gr. 1 | 25÷95 mm2 | 150 mm |
| 3 x AIN 10 Gr. 2 | 120÷240 mm2 | 150 mm |
| 3 x AIN 10 Gr. 3 | 300÷500 mm2 | 150 mm |
| 3 x AIN 20 Gr. 4 | 630÷800 mm2 | 225 mm |
| 3 x AIN 36 Gr. 5 | 1000 mm2 | 405 mm |
| 3 x AIN 36 Gr. 6 | 1200 mm2 | 405 mm |
iMAX VOLTAGE 12-20 kV
| Part No | Section | Core Length |
| 3 x AIN 20 Gr. 1 | 35÷70 mm2 | 225 mm |
| 3 x AIN 20 Gr. 2 | 95÷240 mm2 | 225 mm |
| 3 x AIN 20 Gr. 3 | 300÷500 mm2 | 225 mm |
| 3 x AIN 20 Gr. 4 | 400÷630 mm2 | 225 mm |
| 3 x AIN 36 Gr. 5 | 630÷800 mm2 | 405 mm |
| 3 x AIN 36 Gr. 6 | 1000÷1200 mm2 | 405 mm |
MAX VOLTAGE 18-30 kV
| Part No | Section | Core Length |
| 3 x AIN 30 Gr. 1 | 50÷70 mm2 | 300 mm |
| 3 x AIN 30 Gr. 2 | 95÷240 mm2 | 300 mm |
| 3 x AIN 30 Gr. 3 | 240÷400 mm2 | 300 mm |
| 3 x AIN 36 Gr. 5 | 400÷630 mm2 | 405 mm |
| 3 x AIN 36 Gr. 6 | 630÷1200 mm2 | 405 mm |
MAX VOLTAGE 20.8-36 kV
| Part No | Section | Core Length |
| On Request | 50÷70 mm2 | On Request |
| On Request | 95÷120 mm2 | On Request |
| 3 x AIN 36 Gr. 4 | 150÷300 mm2 | 405 mm |
| 3 x AIN 36 Gr. 5 | 400÷630 mm2 | 405 mm |
| 3 x AIN 36 Gr. 6 | 630÷1200 mm2 | 405 mm |
For Additional Information on Nexans AIN Indoor MV Slip-On Cold Shrink Terminations (Single Core | 42kV), please consult the Technical Data Table or PDF Files below.
*Technical Data subject to change without notice.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
| Ordering Part Number | Nominal Voltage Uo / U (kV) |
Conductor Cross-Section (mm2) - Min. | Conductor Cross-Section (mm2) - Max. | Dia. over Core Insulation (mm) - Min. | Dia. over Core Insulation (mm) - Max. | Number of Sheds |
L (mm) | Dia. D (mm) |
| 3 x AIN 10 Gr. 1 | 6/10 | 25 | 95 | 13.0 | 20.8 | 2 | 150 | 37 |
| 3 x AIN 10 Gr. 2 | 6/10 | 120 | 240 | 19.4 | 28.4 | 2 | 150 | 43 |
| 3 x AIN 10 Gr. 3 | 6/10 | 300 | 500 | 27.7 | 36.4 | 2 | 150 | 60 |
| 3 x AIN 20 Gr. 4 | 6/10 | 630 | 800 | 34.0 | 45.0 | 3 | 225 | 68 |
| 3 x AIN 36 Gr. 5 | 6/10 | 1000 | 1000 | 39.0 | 50.0 | 7 | 405 | 98 |
| 3 x AIN 36 Gr. 6 | 6/10 | 1200 | 1200 | 46.0 | 58.0 | 7 | 405 | 98 |
| 3 x AIN 20 Gr. 1 | 12/20 | 35 | 70 | 18.3 | 23.5 | 3 | 225 | 47 |
| 3 x AIN 20 Gr. 2 | 12/20 | 95 | 240 | 22.5 | 33.0 | 3 | 225 | 56 |
| 3 x AIN 20 Gr. 3 | 12/20 | 300 | 500 | 31.0 | 41.0 | 3 | 225 | 68 |
| 3 x AIN 20 Gr. 4 | 12/20 | 400 | 630 | 34.0 | 45.0 | 3 | 225 | 68 |
| 3 x AIN 36 Gr. 5 | 12/20 | 630 | 800 | 39.0 | 50.0 | 7 | 405 | 98 |
| 3 x AIN 36 Gr. 6 | 12/20 | 1000 | 1200 | 46.0 | 58.0 | 7 | 405 | 98 |
| 3 x AIN 30 Gr. 1 | 18/30 | 50 | 70 | 23.8 | 28.4 | 6 | 300 | 74 |
| 3 x AIN 30 Gr. 2 | 18/30 | 95 | 240 | 27.1 | 37.6 | 6 | 300 | 74 |
| 3 x AIN 30 Gr. 3 | 18/30 | 240 | 400 | 31.5 | 42.8 | 6 | 300 | 81 |
| 3 x AIN 36 Gr. 5 | 18/30 | 400 | 630 | 39.0 | 50.0 | 7 | 405 | 98 |
| 3 x AIN 36 Gr. 6 | 18/30 | 630 | 1200 | 46.0 | 58.0 | 7 | 405 | 98 |
| On Request | 20.8/362 | 50 | 70 | 23.8 | 28.4 | On Request | On Request | On Request |
| On Request | 20.8/362 | 95 | 120 | 27.1 | 32.0 | On Request | On Request | On Request |
| 3 x AIN 36 Gr. 4 | 20.8/362 | 150 | 300 | 31.5 | 41.0 | 7 | 405 | 98 |
| 3 x AIN 36 Gr. 5 | 20.8/362 | 400 | 630 | 39.0 | 50.0 | 7 | 405 | 98 |
| 3 x AIN 36 Gr. 6 | 20.8/362 | 630 | 1200 | 46.0 | 58.0 | 7 | 405 | 98 |
Notes:
The classification does only apply for polymeric insulated XLPE cables (dimensions acc. to DIN VDE 0276-620) with extruded conductive screen. Please contact our sales representative, when using other cable types.
2 Since the dimensions for cables at voltage level 20.8/36 (42) kV are not yet standardised, the conductor cross sections and their assignment of diameters over core insulation given in the table are to be considered as approximate values.
When ordering accessories, we would like to ask you to indicate the checked diameters over core insulation.
Technical Information
- 1. Longitudinally sealed mechanical or compression cable lug
- 2. Silicone tube or cap as additional sealing at the transition of cable lug to the termination housing when using mechanical cable lugs
- 3. High flexibility silicone rubber housing, ensuring a perfect fit to the cable even during load changes
- 4. Integrated conductive rubber insert
- 5. Earth cable lug
- 6. Heat-shrinkable tube
- 7. Heat-shrinkable break-out