3M™ Scotchcast™ Hazardous Area Resin Joint Kit LVI-3/6 (95 – 800mm²)
Product overview
3M™ Scotchcast™ Hazardous Area Resin Joint Kit LVI-3/6 (95 – 800mm²)
The 3M LVI-3/6 Resin Joint Kit is a specialised hazardous-area inline jointing solution for multi-core armoured low-voltage polymeric cables. Designed for Zone 1 & Zone 2 environments, this 3M LVI-3/6 Kit provides advanced electrical insulation, flame-retardant performance and reliable mechanical protection for LV energy cable joints. Each Scotchcast LVI-3/6 (Scotchcast LVI-36) kit includes a transparent two-part mould body with a snap-fit closing system, a flame-retardant phase spacer web and 3M™ Scotchcast™ 1402FR resin packaged in a closed two-chamber mixing system.
Ideal for hazardous industrial sites, the LVI-3/6 Resin Joint delivers safe, consistent installation using either compression or mechanical connectors. The kit also accommodates lead-sheathed cable and PILC transition jointing.
Part Number: 7000092635.
In addition to the Standard Kit, the following options are available:
- LVI‑3/6‑IC – includes Instrumentation & Control Kits
Key Features & Benefits
- Designed for hazardous-area LV multi-core armoured polymeric cables
- Suitable for lead-sheathed cable and PILC transition applications
- Scotchcast 1402FR resin — flame retardant, hydrocarbon resistant, halogen-free
- Transparent two-part mould body with snap-fit closing system
- Clear visual control of connector positions throughout installation
- Flame retardant to UL94 V0
- High chemical resistance, especially against hydrocarbons
- Integrated flame-retardant spacer web ensures correct distances
- Closure cap included to prevent contamination during installation
- Suitable for indoor, outdoor, underground and submerged environments
- Provides strong electrical insulation and long-term mechanical protection
- Includes Scotch™ 23 tape, armour connection components, copper stocking, gloves (EN 394) and full instructions
- Clean and safe handling using the Closed Mix system with dedicated opener
- Each kit is clearly marked for quick identification and traceability
3M LVI-3/6 – Flame-Retardant Hazardous-Area LV Resin Jointing
The 3M LVI-3/6 is a high-integrity, flame-retardant inline solution engineered for the most demanding LV applications. This LVI-3/6 Resin Joint combines the performance of 1402FR resin, a precision-built mould body and a flame-retardant spacer web to ensure dependable sealing and long-term safety in high-risk environments.
As a hazardous-area rated LVI-3/6 Joint Kit, it offers exceptional chemical resistance — particularly to hydrocarbons — making it ideal for petrochemical facilities, refineries, offshore platforms and other sites requiring stringent safety compliance. For installers needing a robust, hazardous-area-ready inline joint, the Scotchcast LVI-3/6 (or LVI-36 Resin Joint) provides proven 3M reliability and extended service life, even in submerged conditions.
For Additional Information on the 3M™ Scotchcast™ Hazardous Area Resin Joint Kit LVI-3/6 (95 – 800mm²), please consult the Technical Data Table or PDF File below.
*Technical Data subject to change without notice.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
| CSA (mm²) | Kit Reference - 1 Core (1kV) |
Kit Reference - 2 Core (1kV) |
Kit Reference - 3 Core (1kV) |
Kit Reference - 4 Core (1kV) |
Kit Reference - 1 Core (3.3kV) |
Kit Reference - 3 Core (3.3kV) |
| 1.5 | - | LVI-3/2-C | LVI-3/2-C | LVI-3/2-C | - | - |
| 2.5 | - | LVI-3/2-C | LVI-3/2-C | LVI-3/2-C | - | - |
| 4 | - | LVI-3/2-C | LVI-3/2-C | LVI-3/2-C | - | - |
| 6 | - | LVI-3/2-C | LVI-3/2-C | LVI-3/2-C | - | - |
| 10 | - | LVI-3/3-C | LVI-3/3-C | LVI-3/3-C | - | - |
| 16 | - | LVI-3/3-C | LVI-3/3-C | LVI-3/3-C | - | LVI-3/4 |
| 25 | - | LVI-3/3-C | LVI-3/4 | LVI-3/4 | - | LVI-3/4 |
| 35 | - | LVI-3/4 | LVI-3/4 | LVI-3/4 | - | LVI-3/4 |
| 50 | LVI-3/2-C | LVI-3/4 | LVI-3/4 | LVI-3/5 | LVI-3/3-C | LVI-3/5 |
| 70 | LVI-3/3-C | LVI-3/5 | LVI-3/5 | LVI-3/5 | LVI-3/3-C | LVI-3/5 |
| 95 | LVI-3/3-C | LVI-3/5 | LVI-3/5 | LVI-3/6 | LVI-3/3-C | LVI-3/6 |
| 120 | LVI-3/4 | LVI-3/5 | LVI-3/6 | LVI-3/6 | LVI-3/4 | LVI-3/6 |
| 150 | LVI-3/4 | LVI-3/6 | LVI-3/7 | LVI-3/7 | LVI-3/4 | LVI-3/6 |
| 185 | LVI-3/4 | LVI-3/6 | LVI-3/7 | LVI-3/7 | LVI-3/4 | LVI-3/7 |
| 240 | LVI-3/5 | LVI-3/7 | LVI-3/7 | LVI-3/8 | LVI-3/5 | LVI-3/7 |
| 300 | LVI-3/5 | LVI-3/7 | LVI-3/7 | LVI-3/8 | LVI-3/5 | LVI-3/8 |
| 400 | LVI-3/5 | LVI-3/7 | LVI-3/8 | LVI-3/8 | LVI-3/5 | LVI-3/8 |
| 500 | LVI-3/5 | - | - | - | LVI-3/5 | - |
| 630 | LVI-3/6 | - | - | - | LVI-3/6 | - |
| 800 | LVI-3/6 | - | - | - | LVI-3/6 | - |
| 1000 | LVI-3/7 | - | - | - | LVI-3/7 | - |
Note: For single core cables using LVI-3/2-C and LVI-3/3-C, the included connectors are not suitable.
Performance Data
Testing
Scotchcast™ Resin Kit Series LVI-3/x tested according to EN50393 Table 3/I/A1
| Type of Test according to EN50393 Table 3 / I / A1 | Results |
| AC Voltage Withstand Test in air 4kV AC/ 1 min |
Passed |
| Insulation Resistance Test in air 1kV DC |
> 10.000MΩ |
| Heat Cycle in air 63 cycles: 5h/3h |
Passed |
| Heat Cycle in water 63 cycles: 5h/3h |
Passed |
| AC Voltage Withstand Test in water 4kV AC/ 1 min |
Passed |
| Insulation Resistance Test in water 1kV DC |
> 10.000MΩ |