CCG E1W Insulated Captive Component Industrial Cable Gland

Product overview

CCG E1W Insulated Captive Component Cable Gland

CCG E1W Insulated Captive Component Cable Gland is a Protective Earth Industrial Cable Gland Device with Dual Seal, designed for Steel Wire Armoured (SWA) and Aluminium Armoured Cable.

CCG E1W Insulated Part Numbers: 0558-0, 055801, 055802, 055803, 055804, 055805, 055806, 055807

Features & Benefits

  • For indoor and outdoor use.
  • Gland is insulated from equipment to prevent system circulating currents.
  • Freely rotating captive cone and inspectible cone ring, providing an inspectible armour clamp and earth bond without twisting the armouring.
  • Patented disconnect armoured clamp system for ease of inspection
  • Provides a seal on the inner and outer sheath of the cable sealing to IP66.
  • Precision manufactured from high-quality brass (nickel plated) available in aluminium or stainless steel 316/316L on request.
  • Complete with thread sealing gasket and with heavy-duty locknut.

CCG E1W Insulated Technical Data

Type: E1W Insulated Protective Earth Industrial Gland
Gland Material: Brass (Nickel Plated), BS 2874, EN 12164, Aluminium ASTM BS221, Stainless Steel 316/316L
Seal Material: Thermoset Elastomer or Silicone on request
Cable Type: Steel Wire Armour and Aluminium Armour Wire
Armour Clamping: Rotating Captive Cone and Inspectible Cone Ring
Sealing Area: Inner Sheath and Outer Sheath
Optional Accessories: Adaptor, Reducer, Earth Tag, Locknut, Serrated Washer and Shroud

Installation Standards

  • AS/NZS 3000
  • BS 6121-5
  • BS 7671
  • BS 7430
  • IEC 60364-5-54
  • SANS 0142

Additional Technical Data of E1W Insulated Captive Component Cable Gland part numbers can be found on the table below. For Standards, Certifications & Fitting Instructions, please advise PDF Files.

FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929

Technical Data

Product Code Gland Size Ref.  Metric Entry Thread (C) Metric Entry Thread (Min D) Cable Detail (Min A) Cable Detail (Max A) Cable Detail (Min B) Cable Detail (Max B) Max Length (E) Armour Dia
(Min F)
Armour Dia
(Max F)
Hexagonal Detail
(Max Flats)
Hexagonal Detail
(Max Crns)
Installation Torque Value (Nm)
0558-0 0-20s 20 10 7.0 12.0 11.5 16.0 61.0 0.90 1.25 ♥ 24 ♥ 27 35.0
055801 1-20 20 10 9.0 13.5 14.5 20.5 67.0 0.90 1.25 27 30 35.0
055802 2-25 25 10 14.0 17.5 20.5 26.5 80.0 1.25 1.60 35 39 50.0
055803 3-32 32 10 19.0 24.0 26.5 33.5 80.0 1.60 2.00 42 47 70.0
055804 4-40 40 10 26.0 34.0 33.0 42.5 85.0 1.60 2.00 52 59 90.0
055805 5-50 50 10 34.0 42.5 42.5 52.5 106.0 2.00 2.50 65 73 100.0
055806 6-63 63 10 44.0 55.5 52.5 65.5 129.0 2.00 2.50 80 90 120.0
055807 7-75 75 10 56.0 68.0 65.5 78.0 149.0 2.50 3.15 96 108 120.0

All dimensions are in mm.

♥ : When manufactured in Aluminium, Hex will be 27 Across Flats and 30 Across Corners.

CCG E1W Insulated Captive Component Gland Diagram

 

Find out more about our products or becoming a supplier