Nexans Euromold 400AR-4 Equipment Bushing
Product overview
Nexans Euromold 400AR-4 Equipment Bushing
Nexans Euromold 400AR-4/ K400AR-4 / M400AR-4 Equipment Bushings are MV-HV Bushings for use in equipment insulated with oil fluid, typically for switchgear, capacitors, motors that are specified to terminate and connect medium/high voltage cables in the following voltage classes:
- 6/10 (12kV)
- 6.35/11 (12kV)
- 8.7/15 (17.5kV)
- 12/20 (24kV)
- 12.7/22 (24kV)
- 18/30 (36kV)
- 19/33 (36kV)
Technical Characteristics
- Each bushing is tested for AC withstand and partial discharge prior to leaving the factory.
- The bolted type equipment bushings are moulded epoxy insulated parts and meet the requirements of CENELEC EN 50180 and IEC 60137.
Specification & Design
To order the equipment bushing, specify the type. The bushings can be supplied with an earth jumper (/J) or an earth plate (/GS). This earth connection must be specified when ordering (e.g. M400AR-4/J):
Euromold Equipment Bushing Type |
Voltage Um |
Current Ir |
Creepage Length A-B |
400AR-4 | 12 kV | 1250 Amps | 315 mm |
K400AR-4 | 24 kV | 1250 Amps | 315 mm |
M400AR-4 | 36 kV | 1250 Amps | 315 mm |
Note: For dimensions of the above bushing types, refer to the Technical Data Table below.
Nexans Euromold 400AR-4 Fixings for Bushings
For Ordering Instructions and Part Number Selection Table of Nexans Euromold 400AR-4/ K400AR-4 /M400AR-4 Equipment Bushings, please refer to the Technical Data Table Below. For additional General and Technical Information, download PDF File.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
ORDERING INSTRUCTIONS To order the equipment bushing, specify the type. The bushings can be supplied with an earth jumper (/J) or an earth plate (/GS). This earth connection must be specified when ordering (e.g. M400AR-4/J): |
EQUIPMENT BUSHING TYPE | VOLTAGE Um |
CURRENT Ir |
A | B | C | D | E | Dia. F | Dia. G | Dia. H |
400AR-4 | 12 kV | 1250 Amps | 329 mm | 138 mm | 36 mm | M16 | 40 mm | 100 mm | 150 mm | 32 mm |
K400AR-4 | 24 kV | 1250 Amps | 329 mm | 138 mm | 36 mm | M16 | 40 mm | 100 mm | 150 mm | 32 mm |
M400AR-4 | 36 kV | 1250 Amps | 329 mm | 138 mm | 36 mm | M16 | 40 mm | 100 mm | 150 mm | 32 mm |