Nexans Euromold 400LR Separable Elbow Connector
Product overview
Nexans Euromold 400LR Separable Elbow Connector
Nexans Euromold 400LR Separable Elbow Connector with 400A Current Rating is an elbow connector designed for Interface B and covers voltages from 11/12kV to 33/36kV with a maximum conductor size of 240sqmm. The separable connector connects polymeric insulated cable to equipment (transformers, switchgear, motors, etc.) and meets the requirements of CENELEC HD 629,1.
Type 400LR Part Numbers: 400LR/G, K400LR/G, M400LR/G.
Euromold 400LR is a screened separable elbow connector specified to terminate and connect medium/high voltage cables onto Interface B bushings in the following voltage classes:
- 6/10 (12kV)
- 6.35/11 (12kV)
- 8.7/15 (17.5kV)
- 12/20 (24kV)
- 12.7/22 (24kV)
- 18/30 (36kV)
- 19/33 (36kV)
Technical Characteristics
- The thick conductive EPDM jacket provides a total safe to touch screen which ensures safety for personnel.
- Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
Specification & Design
Euromold Type 400LR |
Voltage Um |
Current Ir |
Conductor Size Min |
Conductor Size Max |
400LR/G | 12 kV | 400 Amps | 50 | 240 |
K400LR/G | 24 kV | 400 Amps | 25 | 240 |
M400LR/G | 36 kV | 400 Amps | 35 | 185 |
Separable connector comprising:
- Conductive EPDM insert.
- Conductive EPDM jacket.
- Insulating EPDM layer moulded between the insert and the jacket.
- Type B – interface as described by CENELEC EN 50180 and 50181.
- Conductor connector.
- Cable reducer.
- Earthing lead.
- VD point.
- Conductive rubber cap.
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
400LR Elbow Connector Kit Contents
The complete (K)(M)400LR/G elbow connector kit comprises the following components. The kit also comprises silicon grease, gloves, wipers and installation instructions.
For Ordering Instructions and Part Number Selection Table of Nexans Euromold 400LR Elbow Connectors (400LR/G, K400LR/G, M400LR/G), please refer to the Technical Data Table Below. For additional General and Technical Information, download PDF File.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
ORDERING INSTRUCTIONS FOR (K)(M)400LR/G
To order the elbow connector, select the part number which gives the best centring to the cable core insulation diameter and substitute X using table X, according to the conductor size and type. Add a 'K' for use up to 24 kV and add an 'M' for use up to 36 kV. Example: The copper wire screened cable is 24 kV, 185 mm2 stranded copper with a diameter over core insulation of 27.5 mm. Order a K400LR/G-018-95.240UN5 elbow connector kit. |
PART NUMBER | DIAMETER OVER CORE INSULATION MIN | DIAMETER OVER CORE INSULATION MAX |
400LR/G-011-X | 12 mm | 19 mm |
400LR/G-015-X | 16 mm | 26.5 mm |
400LR/G-018-X | 19 mm | 32.6 mm |
400LR/G-021-X | 22 mm | 34.6 mm |
400LR/G-027-X | 28.5 mm | 37.5 mm |
TABLE X - ALUMINIUM & COPPER CONDUCTOR |
CONDUCTOR SIZE | BOLTED | BOLTED |
25 mm2 | 25.95UN5 | |
35 mm2 | 25.95UN5 | |
50 mm2 | 25.95UN5 | |
70 mm2 | 25.95UN5 | |
95 mm2 | 25.95UN5 | 25.240UN5 |
120 mm2 | 25.240UN5 | |
150 mm2 | 25.240UN5 | |
185 mm2 | 25.240UN5 | |
240 mm2 | 25.240UN5 |