Nexans Euromold 440PB Coupling Connector
Product overview
Nexans Euromold 440PB Separable Coupling Connector
Nexans Euromold 440PB Separable Coupling Connector is a coupling connector (bolted type) for dual arrangement. Designed to be used with 400TB and 440TB Separable Tee Connector and meets the requirements of CENELEC HD 629,1.
Type 440PB Part Numbers: 440PB/G, K440PB/G, M440PB/G, P440PB/G.
Euromold 440PB is a bolted separable coupling connector specified to terminate and connect medium/high voltage cables in the following voltage classes:
- 6/10 (12kV)
- 6.35/11 (12kV)
- 8.7/15 (17.5kV)
- 12/20 (24kV)
- 12.7/22 (24kV)
- 18/30 (36kV)
- 19/33 (36kV)
- 20.8/36 (42kV)
Technical Characteristics
- A thick conductive EPDM jacket provides a total safe to touch screen which ensures safety for personnel.
- Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
Specification & Design
The 440PB separable connector meets the requirements of CENELEC HD 629.1 S1.
Euromold Type 440PB |
Voltage Um |
Current Ir |
Conductor Size Min |
Conductor Size Max |
440PB/G | 12 kV | 800 Amps | 185 mm2 | 630 mm2 |
K440PB/G | 24 kV | 800 Amps | 185 mm2 | 630 mm2 |
M440PB/G | 36 kV | 800 Amps | 185 mm2 | 630 mm2 |
P440PB/G | 42 kV | 800 Amps | 185 mm2 | 630 mm2 |
Separable connector comprising:
- Interface designed to fit 400TB/ 440TB connector
- Contact rod for 440PB
- Conductive EPDM insert
- Insulating EPDM layer moulded between the insert and the jacket
- Conductive EPDM jacket
- Conductive EPDM cap
- Basic insulating plug
- Conductor contact
- Cable reducer
- Earthing lead
- Threaded M16 stud for the equipment bushing
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
440PB Coupling Connector Kit Contents
The complete (K)(M)(P)440PB/G coupling connector kit comprises 3 x the following components. The kit also comprises silicone grease, field control mastic, installation rod, installation instructions and crimp chart.
For Ordering Instructions and Part Number Selection Table of Nexans Euromold 440PB Separable Coupling Connector (440PB/G, K440PB/G, M440PB/G, P440PB/G), please refer to the Technical Data Table Below. For additional General and Technical Information, download PDF File.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
ORDERING INSTRUCTIONS FOR (K)(M)(P)440PBTo order the coupling connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV and a 'P' for use up to 42 kV. Example: The copper wire screened cable is 36 kV, 240 mm2 stranded copper with a diameter over core insulation of 37 mm. Order 3 x M440PB/G-32-240(K) M-12-2 coupling connector kit. |
PART NUMBER | DIAMETER OVER CORE INSULATION MIN | DIAMETER OVER CORE INSULATION MAX |
3 x 440PB/G-22-X | 23.5 mm | 31 mm |
3 x 440PB/G-27-X | 28.5 mm | 37.5 mm |
3 x 440PB/G-32-X | 34 mm | 42.5 mm |
3 x 440PB/G-37-X | 39 mm | 48.5 mm |
3 x 440PB/G-43-X | 45.5 mm | 56 mm |
TABLE X - CONNECTORS SUITABLE FOR COPPER & ALUMINIUM CABLES |
CONDUCTOR SIZE | ALU CONDUCTOR DIN HEX |
ALU CONDUCTOR DEEP INDENT |
ALU & CU CONDUCTOR BOLTED |
CU CONDUCTOR DIN HEX |
185 mm2 | 185(K)M-12-2 | 185KM-12-1 | 185.400-14-5 | 185(K)M-11-2 |
240 mm2 | 240(K)M-12-2 | 240KM-12-1 | 185.400-14-5 | 240(K)M-11-2 |
300 mm2 | 300(K)M-12-2 | 300KM-12-1 | 185.400-14-5 | 300(K)M-11-2 |
400 mm2 | 400(K)M-12-2 | 400KM-12-1 | 185.400-14-5, 400.630-14-5 | 400(K)M-11-2 |
500 mm2 | 500(K)M-12-2 | 500KM-12-1 | 400.630-14-5 | 500(K)M-11-2 |
630 mm2 | - | 630KM-12-1 | 400.630-14-5 | 630(K)M-11-2 |