Prysmian BICON E1WF Cable Gland (472AA Series) (e.g. 472AA-52)

Product overview

Prysmian BICON E1WF Cable Gland (472AA Series) is a brass indoor and outdoor cable gland for use in hazardous locations. Suitable for use with all steel wire armoured cables.
Part Numbers: 472AA-51, 472AA-71, 472AA-52, 472AA-53, 472AA-55, 472AA-56, 472AA-57, 472AA-58, 472AA-59, 472AA-60, 472AA-61, 472AA-62, 472AA-63, 472AA-64.

Prysmian 472AA Features

  • Brass indoor and outdoor cable gland for use in hazardous areas.
  • Suitable for circular, galvanized steel wire armour cables with extruded polymeric bedding and oversheath.
  • Achieves IP66 seal onto cable and to enclosure with suitable sealing washer or thread sealant.
  • Three part armour lock provides mechanical cable retention and electrical continuity.
  • Inner PCP seal grips cable bedding and provides additional ingress protection.
  • Suitable for most climatic conditions – weatherproof and waterproof.
  • Standard and Nickel plated versions available.
  • Full installation instructions supplied.

Technical Data

  • Certified II 2GD, Ex e II & Ex d IIC under ATEX directive 94/9/EC.
  • Atex Compliance Standards: EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1.
  • Certificate number Sira 02ATEX3092X.
  • IECEx Compliance Standards: IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
  • Certificate number IECEx SIR 10.0071X
  • Service temperature range -60°C to +90°C.

Additional Information

May be used in:

  • Zones 0 , 1 & 2 with Ex ia IIA , B & C equipment.
  • Zones 1 & 2 with Ex ib IIA , B & C equipment.
  • Zones 1 & 2 with Ex e II equipment.
  • Zone 2 with Ex nA II equipment.
  • Zones 21 & 22 with Ex tD A21.

Where the cable is effectively filled, may also be used in:

  • Zones 1 & 2 with Ex d IIC equipment not containing a source of ignition & with a volume less than 2000 cm3.
  • Zones 1 & 2 with Ex d IIA & Ex d IIB equipment not containing a source of ignition & with any volume.
  • Zone 1 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with a volume less than 2000 cm.
  • Zone 2 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with any volume.
  • Zone 2 with Ex nR II equipment.

For more information on Prysmian BICON E1WF Cable Gland (472AA Series) (e.g. 472AA-52), please consult Datasheet below.

FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929

Technical Data

Design Reference (Standard) Design Reference (Nickel Plated) Size (Metric) Under Armour Min Ø (A) Under Armour Max Ø (A) Overall Ø (B) Min Overall Ø (B) Max Armour Wire Ø Entry Thread (D) Thread Length (E) Protrusion Length (F)  Hexagon A/F (G) Hexagon A/C (H)
472AA-51 472AA-51V 16 3.8 8.7 8.0 13.2 0.9 M16 x 1.5 15 41 23.4 26.7
472AA-71 472AA-71V 20SS 3.8 8.7 8.0 13.2 0.9 M20 x 1.5 15 41 23.4 26.7
472AA-52 472AA-52V 20S 8.0 11.8 8.0 15.8 0.9/1.25 M20 x 1.5 15 43 25.7 29.2
472AA-53 472AA-53V 20 11.8 14.2 11.7 20.8 0.9/1.25 M20 x 1.5 15 43 30.5 34.0
472AA-55 472AA-55V 25 14.0 20.1 17.0 27.2 1.25/1.6 M25 x 1.5 15 48 37.6 42.2
472AA-56 472AA-56V 32 19.7 26.6 23.5 33.5 1.6/2.0 M32 x 1.5 15 53 47.2 53.6
472AA-57 472AA-57V 40 26.6 32.4 29.0 39.9 1.6/2.0 M40 x 1.5 15 56 56.4 61.5
472AA-58 472AA-58V 50S 32.4 38.4 38.0 46.2 2.0/2.5 M50 x 1.5 15 61 60.0 66.0
472AA-59 472AA-59V 50 38.4 44.3 39.5 52.6 2.0/2.5 M50 x 1.5 15 61 70.1 77.2
472AA-60 472AA-60V 63S 44.3 50.3 50.0 58.9 2.5 M63 x 1.5 15 64 75.0 83.0
472AA-61 472AA-61V 63 50.3 56.2 51.3 65.3 2.5 M63 x 1.5 15 64 80.0 87.4
472AA-62 472AA-62V 75S 56.2 62.2 62.0 71.6 2.5 M75 x 1.5 15 73 90.2 99.1
472AA-63 472AA-63V 75 62.2 68.1 62.5 78.0 2.5 M75 x 1.5 15 73 98.8 109.2
472AA-64 472AA-64V 85 68.0 74.0 68.0 88.0  3.15 M85 x 2.0 20 102 115.1 126.0

Technical Information

  • Certified II 2GD, Ex e II & Ex d IIC under ATEX directive 94/9/EC.
  • Atex Compliance Standards: EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1.
  • Certificate number Sira 02ATEX3092X.
  • IECEx Compliance Standards: IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
  • Certificate number IECEx SIR 10.0071X
  • Service temperature range -60°C to +90°C.
E1WF Ex d IIC - Ex e II Cable Gland 472AA Series technical

Additional Information

May be used in:

  • Zones 0 , 1 & 2 with Ex ia IIA , B & C equipment.
  • Zones 1 & 2 with Ex ib IIA , B & C equipment.
  • Zones 1 & 2 with Ex e II equipment.
  • Zone 2 with Ex nA II equipment.
  • Zones 21 & 22 with Ex tD A21.

Where the cable is effectively filled, may also be used in:

  • Zones 1 & 2 with Ex d IIC equipment not containing a source of ignition & with a volume less than 2000 cm3.
  • Zones 1 & 2 with Ex d IIA & Ex d IIB equipment not containing a source of ignition & with any volume.
  • Zone 1 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with a volume less than 2000 cm.
  • Zone 2 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with any volume.
  • Zone 2 with Ex nR II equipment.

 

 

Find out more about our products or becoming a supplier