Prysmian BICON E1WF-Al Cable Gland (455AA)
Product overview
Prysmian BICON E1WF-Al Cable Gland (455AA Series) is an aluminium indoor and outdoor cable gland for use in hazardous locations. Suitable for use with all aluminium wire armoured cables.
Part Numbers: 455AA-51, 455AA-71, 455AA-52, 455AA-53, 455AA-55, 455AA-56, 455AA-57, 455AA-58, 455AA-59, 455AA-60, 455AA-61, 455AA-62, 455AA-63, 455AA-64.
Prysmian 455AA Features
- Aluminium indoor and outdoor cable gland for use in hazardous areas.
- Suitable for circular, aluminium steel wire armour cables with extruded polymeric bedding and oversheath.
- Achieves IP66 seal onto cable and to enclosure with suitable sealing washer or thread sealant.
- Three part armour lock provides mechanical cable retention and electrical continuity.
- Inner PCP seal grips cable bedding and provides additional ingress protection.
- Suitable for most climatic conditions – weatherproof and waterproof.
- Standard and Nickel plated versions available.
- Full installation instructions supplied.
Technical Data
- Certified II 2GD, Ex e II & Ex d IIC under ATEX directive 94/9/EC.
- Atex Compliance Standards: EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1.
- Certificate number Sira 02ATEX3092X.
- IECEx Compliance Standards: IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
- Certificate number IECEx SIR 10.0071X
- Service temperature range -60°C to +90°C.
Additional Information
May be used in:
- Zones 0 , 1 & 2 with Ex ia IIA , B & C equipment.
- Zones 1 & 2 with Ex ib IIA , B & C equipment.
- Zones 1 & 2 with Ex e II equipment.
- Zone 2 with Ex nA II equipment.
- Zones 21 & 22 with Ex tD A21.
Where the cable is effectively filled, may also be used in:
- Zones 1 & 2 with Ex d IIC equipment not containing a source of ignition & with a volume less than 2000 cm3.
- Zones 1 & 2 with Ex d IIA & Ex d IIB equipment not containing a source of ignition & with any volume.
- Zone 1 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with a volume less than 2000 cm.
- Zone 2 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with any volume.
- Zone 2 with Ex nR II equipment.
For more information on Prysmian BICON E1WF-Al Cable Gland (455AA Series), please consult Datasheet below.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
Design Reference (Standard) | Size (Metric) | Under Armour Min Ø (A) | Under Armour Max Ø (A) | Overall Ø (B) Min | Overall Ø (B) Max | Armour Wire Ø | Entry Thread (D) | Thread Length (E) | Protrusion Length (F) | Hexagon A/F (G) | Hexagon A/C (H) |
455AA-51 | 16 | 3.8 | 8.7 | 8.0 | 13.2 | 0.9 | M16 x 1.5 | 15 | 41 | 23.4 | 26.7 |
455AA-71 | 20SS | 3.8 | 8.7 | 8.0 | 13.2 | 0.9 | M20 x 1.5 | 15 | 41 | 23.4 | 26.7 |
455AA-52 | 20S | 8.0 | 11.8 | 8.0 | 15.8 | 0.9/1.25 | M20 x 1.5 | 15 | 43 | 25.7 | 29.2 |
455AA-53 | 20 | 11.8 | 14.2 | 11.7 | 20.8 | 0.9/1.25 | M20 x 1.5 | 15 | 43 | 30.5 | 34.0 |
455AA-55 | 25 | 14.0 | 20.1 | 17.0 | 27.2 | 1.25/1.6 | M25 x 1.5 | 15 | 48 | 37.6 | 42.2 |
455AA-56 | 32 | 19.7 | 26.6 | 23.5 | 33.5 | 1.6/2.0 | M32 x 1.5 | 15 | 53 | 47.2 | 53.6 |
455AA-57 | 40 | 26.6 | 32.4 | 29.0 | 39.9 | 1.6/2.0 | M40 x 1.5 | 15 | 56 | 56.4 | 61.5 |
455AA-58 | 50S | 32.4 | 38.4 | 38.0 | 46.2 | 2.0/2.5 | M50 x 1.5 | 15 | 61 | 60.0 | 66.0 |
455AA-59 | 50 | 38.4 | 44.3 | 39.5 | 52.6 | 2.0/2.5 | M50 x 1.5 | 15 | 61 | 70.1 | 77.2 |
455AA-60 | 63S | 44.3 | 50.3 | 50.0 | 58.9 | 2.5 | M63 x 1.5 | 15 | 64 | 75.0 | 83.0 |
455AA-61 | 63 | 50.3 | 56.2 | 51.3 | 65.3 | 2.5 | M63 x 1.5 | 15 | 64 | 80.0 | 87.4 |
455AA-62 | 75S | 56.2 | 62.2 | 62.0 | 71.6 | 2.5 | M75 x 1.5 | 15 | 73 | 90.2 | 99.1 |
455AA-63 | 75 | 62.2 | 68.1 | 62.5 | 78.0 | 2.5 | M75 x 1.5 | 15 | 73 | 98.8 | 109.2 |
455AA-64 | 85 | 68.0 | 74.0 | 68.0 | 88.0 | 3.15 | M85 x 2.0 | 20 | 102 | 115.1 | 126.0 |
Technical Information
- Certified II 2GD, Ex e II & Ex d IIC under ATEX directive 94/9/EC.
- Atex Compliance Standards: EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1.
- Certificate number Sira 02ATEX3092X.
- IECEx Compliance Standards: IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
- Certificate number IECEx SIR 10.0071X
- Service temperature range -60°C to +90°C.
Additional Information
May be used in:
- Zones 0 , 1 & 2 with Ex ia IIA , B & C equipment.
- Zones 1 & 2 with Ex ib IIA , B & C equipment.
- Zones 1 & 2 with Ex e II equipment.
- Zone 2 with Ex nA II equipment.
- Zones 21 & 22 with Ex tD A21.
Where the cable is effectively filled, may also be used in:
- Zones 1 & 2 with Ex d IIC equipment not containing a source of ignition & with a volume less than 2000 cm3.
- Zones 1 & 2 with Ex d IIA & Ex d IIB equipment not containing a source of ignition & with any volume.
- Zone 1 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with a volume less than 2000 cm.
- Zone 2 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with any volume.
- Zone 2 with Ex nR II equipment.