CCG E1EX Lead Seal Cable Gland (0523)
Product overview
CCG E1EX Lead Seal Cable Gland (0523)
CCG E1EX Lead Seal Cable Gland (0523) is a Hazardous Area Glanding Device for Lead Sheathed Armoured Cable. Suitable for indoors, outdoors, Group II, III, Zone 1, 2, 20, 21 and 22 hazardous areas.
CCG Part Numbers: 052300-LS, 0523-0-LS, 052301-LS, 052322-LS, 052302-LS, 052333-LS, 052303-LS, 052344-LS, 052304-LS, 052355-LS, 052305-LS, 052366-LS, 052306-LS, 052306L-LS, 052377-LS, 052307-LS, 052307L-LS, 052308-LS, 052399-LS, 052309-LS, 052310-LS, 052311-LS, 052312-LS, 052313-LS
Features & Benefits
- For indoors, outdoors, Group II, III, Zone 1, 2, 20, 21 and 22 hazardous areas.
- Two-part handling, no loose parts.
- Provides 360° earthing to the lead sheath.
- Freely rotating captive cone ring, providing an armour clamp and earth bond without twisting the armour wires.
- Freely rotating captive cone and inspectible cone ring and an armour clamp and earth bond for steel wire armour.
- Factory fitted with a specially formulated elastomeric seal for Built-in Safety™, lead seals on the lead sheath to IP65/66/68.
- Precision manufactured from high-quality brass (Marine Grade Electroless Nickel Plated™) available in aluminium or stainless steel 316/316L on request.
- Supplied with a thread sealing gasket (parallel threads only).
CCG E1EX Lead Seal Technical Data
Type: E1EX Lead Seal
Equipment Protection Levels: Ex db IIC, Ex eb IIC, Ex ta IIIC, Ex nR IIC
Gland Material: Brass (Marine Grade Electroless Nickel Plated™), Stainless Steel 316/316L
Seal Material: Standard Thermoset Elastomer or Extreme Temperature Seals and Lead
Sealing Gasket Material: HDPE, Nylon 66 or PTFE
Cable Type: Steel Wire Armour, Lead Sheath
Armour Clamping: Rotating Captive Cone and Inspectible Cone Ring
Sealing Area: Inner Lead Sheath, Outer Sheath
Optional Accessories: Adaptor, Reducer, Earth Tag, Locknut, Serrated Washer and Shroud
Note: The installer should ensure that the materials are suitable for the installation environment.
Installation Standards
- IEC/BS EN
- IECEx
- ATEX
- UKEX
- CCC/CNEx (China)
- SANS
- Ingress Protection
- Deluge Protection
- Corrosion Protection
- Marine ABS
- DNV-GL
Hazardous Areas
A Hazardous Area is one in which there is potential for an explosion of gases, vapours, mists or dust or a combination of these. Such locations are petrochemical plants, offshore oil rigs, fuel filling stations, timber mills, coal mines, flour mills, paint spray booths, sewerage treatment plants, hospitals, explosive magazines and more.
Special precautions must be taken for the design, manufacture, installation and use of equipment and cable glands in such hazardous areas. Persons involved in selecting installing and maintaining electrical equipment for use in hazardous areas should be competently trained, have a full understanding of what a hazardous area is and have knowledge of the equipment protection levels and the installation standards involved.
Additional Technical Data on CCG E1EX Lead Seal Cable Gland (0523) Part Numbers can be found on the table below. For Conforming Standards & Certificates as well as Fitting Instructions, please advise PDF File.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
Product Code | Gland Size Ref. | Metric Entry Thread (C) | Metric Entry Thread (Min D) | NPT Entry Thread (C) | NPT Entry Thread (Min D) | Cable Detail Lead Sheath (Min A) | Cable Detail Lead Sheath (Max A) | Cable Detail (Min B) | Cable Detail (Max B) | Max Length (E) | Armour Dia (Min F) | Armour Dia (Max F) | Hexagonal Detail (Max Flats) | Hexagonal Detail (Max Crns) | Installation Torque Value (Nm) |
052300-LS | 00-20ss | M20x1.5 | 15 | ½/¾ | 15 | 3 | 8 | 8 | 13.5 | 53 | 0.20 | 0.90 | 24/27 | 27/30 | 35 |
0523-0-LS | 0-20s | M20x1.5 | 15 | ½/¾ | 15 | 8 | 12 | 11.5 | 16 | 53 | 0.20 | 1.25 | 24/27 | 27/30 | 35 |
052301-LS | 1-20 | M20x1.5 | 15 | ½/¾ | 15 | 11 | 15 | 14.5 | 20.5 | 56 | 0.20 | 1.25 | 27 | 30 | 35 |
052322-LS | 2s-25s | M25x1.5 | 15 | ¾/1 | 15/19 | 13 | 16.5 | 16 | 24.5 | 60 | 0.20 | 1.60 | 35 | 39 | 50 |
052302-LS | 2-25 | M25x1.5 | 15 | ¾/1 | 15/19 | 13 | 16.5 | 20.5 | 26.5 | 60 | 0.20 | 1.60 | 35 | 39 | 50 |
052333-LS | 3s-32s | M32x1.5 | 15 | 1/1¼ | 19 | 16 | 19 | 23 | 30.5 | 66 | 0.20 | 2.00 | 42 | 47 | 70 |
052303-LS | 3-32 | M32x1.5 | 15 | 1/1¼ | 19 | 18 | 20.5 | 26.5 | 33.5 | 66 | 0.20 | 2.00 | 42 | 47 | 70 |
052344-LS | 4s-40s | M40x1.5 | 15 | 1¼/1½ | 19/21 | 20.5 | 25 | 30 | 39.5 | 78 | 0.30 | 2.00 | 52 | 59 | 90 |
052304-LS | 4-40 | M40x1.5 | 15 | 1¼/1½ | 19/21 | 25 | 29 | 33 | 42.5 | 78 | 0.30 | 2.00 | 52 | 59 | 90 |
052355-LS | 5s-50s | M50x1.5 | 15 | 1½/2 | 21 | 28.5 | 34 | 34 | 47.5 | 87 | 0.40 | 2.50 | 65 | 73 | 100 |
052305-LS | 5-50 | M50x1.5 | 15 | 1½/2 | 21 | 33.5 | 36 | 42.5 | 52.5 | 87 | 0.40 | 2.50 | 65 | 73 | 100 |
052366-LS | 6s-63s | M63x1.5 | 15 | 2/2½ | 21/30 | 35.5 | 39 | 45.5 | 60.5 | 110 | 0.40 | 2.50 | 80 | 90 | 120 |
052306-LS | 6m-63m | M63x1.5 | 15 | 2/2½ | 21/30 | 38.5 | 42 | 52.5 | 65.5 | 110 | 0.40 | 2.50 | 80 | 90 | 120 |
052306L-LS | 6L-63L | M63x1.5 | 15 | 2/2½ | 21/30 | 41.5 | 44 | 52.5 | 65.5 | 110 | 0.40 | 2.50 | 80 | 90 | 120 |
052377-LS | 7s-75s | M75x1.5 | 15 | 2½/3 | 30/32 | 43 | 49 | 57 | 72.5 | 118 | 0.40 | 3.15 | 96 | 108 | 120 |
052307-LS | 7m-75m | M75x1.5 | 15 | 2½/3 | 30/32 | 49 | 56 | 65.5 | 78 | 118 | 0.40 | 3.15 | 96 | 108 | 120 |
052307L-LS | 7L-75L | M75x1.5 | 15 | 2½/3 | 30/32 | 56 | 59 | 65.5 | 78 | 118 | 0.40 | 3.15 | 96 | 108 | 120 |
052308-LS | 8-80 | M80x2.0 | 15 | 3 | 32 | 59 | 66 | 65 | 77.5 | 175 | 2.50 | 3.15 | 96 | 108 | 120 |
052399-LS | 9s-90s | M90x2.0 | 15 | 3/3½ | 32/33 | 66 | 73 | 73 | 86.5 | 184 | 3.00 | 4.00 | 111 | 125 | 120 |
052309-LS | 9-90 | M90x2.0 | 15 | 3/3½ | 32/33 | 73 | 79 | 82 | 90.5 | 184 | 3.00 | 4.00 | 111 | 125 | 120 |
052310-LS | 10-100 | M100x2.0 | 15 | 3½/4 | 33/34 | 78 | 88 | 91 | 100 | 189 | 3.00 | 4.00 | 125 | 141 | 120 |
052311-LS | 11-115 | M115x2.0 | 15 | 4 | 34 | 86 | 96 | 100 | 114 | 189 | 3.00 | 4.00 | 135 | 152 | 175 |
052312-LS | 12-120 | M120x2.0 | 15 | - | - | 96 | 100 | 103 | 118 | 189 | 3.00 | 4.00 | 140 | 158 | 175 |
052313-LS | 13-130 | M130x2.0 | 15 | - | - | 100 | 112 | 113 | 124 | 189 | 3.00 | 4.00 | 146 | 164 | 175 |
All dimensions except NPT are in mm. Exact dimensions of the cable lead sheath must be submitted to CCG before ordering. Intermediate thread sizes are available on request. NPT threads should be tightened ‘wrench tight’. |