Nexans Euromold 200SR Separable Straight Connector
Product overview
Nexans Euromold 200SR Separable Straight Connector
Nexans Euromold 200SR Separable Straight Connector with 250A Current Rating is a straight connector designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, etc.). Meets the requirements of CENELEC HD 629,1.
Type 200SR Part Numbers: K200SR-12, K200SR-16.
Euromold 200SR is a separable straight connector specified to terminate and connect medium/high voltage cables onto Interface A bushings in the following voltage classes:
- 6/10 (12kV)
- 6.35/11 (12kV)
- 8.7/15 (17.5kV)
- 12/20 (24kV)
- 12.7/22 (24kV)
Technical Characteristics
- A thick conductive EPDM jacket provides a total safe to touch screen, ensuring personnel safety.
- Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
Specification & Design
Euromold Type 200SR |
Voltage Um |
Current Ir |
Conductor Size Min-Max |
Diam. Over Insulation |
K200SR-12 | 12 kV 17,5 kV |
250 Amps 250 Amps |
25-95 mm2 25-50 mm2 |
13-21 mm 13-21 mm |
K200SR-16 | 17,5 kV 24 kV |
250 Amps 250 Amps |
50-95 mm2 25-95 mm2 |
17,5-25 mm 17,5-25 mm |
Separable connector comprising:
- Conductive EPDM insert.
- Conductive EPDM jacket.
- Insulating EPDM layer.
- Type A interface as described by CENELEC EN 50180 and 50181.
- Conductor contact.
- Earthing lead.
- Cable reducer.
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
200SR Straight Connector Kit Contents
The complete K200SR Straight connector kit comprises 3 x the following components. The kit also comprises silicon grease, water sealing mastic, gloves, wipers, adhesive tape and installation instructions.
For Ordering Instructions and Part Number Selection Table of Nexans Euromold 200SR Straight Connectors (K200SR-12, K200SR-16), please refer to the Technical Data Table Below. For additional General and Technical Information, download PDF File.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
ORDERING INSTRUCTIONS FOR K200SR/G
To order a kit of 3 x straight connectors, specify the type:
Example: The cable is 24 kV, 50 mm2 compact stranded aluminium with a diameter over core insulation of 20.5 mm and copper screen wires. Order 3 x (K200SR-16) straight connector kit. Additional Options Voltage Detection Point: A version with a capacitive voltage divider (for voltage detection) and pre-moulded groove (for locking ring installation) is also available. Simply add -VD to the specified type. |
PART NUMBER | CURRENT (Ir) | VOLTAGE (Um) | CONDUCTOR SIZES | DIAMETER OVER CORE INSULATION |
3 x (K200SR-16-120.150) | 250 Amps | 12 kV | 120 - 150 mm2 | 17,5 - 25 mm |
3 x (K200SR-19-120.150) | 250 Amps | 17,5-24 kV | 120 - 150 mm2 | 21.5 - 28,5 mm |