Nexans Euromold 489TB Separable Tee Connector
Product overview
Nexans Euromold 489TB Separable Tee Connector
Nexans Euromold 489TB Separable Tee Connector is a tee-connector (bolted type) used to terminate MV-HV XLPE/EPR (polymeric) insulated cables up to 42kV to electrical equipment (transformers, switchgear, motors, etc.). Meets the requirements of CENELEC HD 629,1. Also used to connect cable to cable when using the appropriate mating parts.
Type 489TB Part Numbers: 489TB/G, K489TB/G, M489TB/G, P489TB/G.
Euromold 489TB is a bolted separable tee connector specified to terminate and connect medium/high voltage cables in the following voltage classes:
- 6/10 (12kV)
- 6.35/11 (12kV)
- 8.7/15 (17.5kV)
- 12/20 (24kV)
- 12.7/22 (24kV)
- 18/30 (36kV)
- 19/33 (36kV)
- 20.8/36 (42kV)
Technical Characteristics
- A thick conductive EPDM jacket provides a total safe to touch screen which ensures safety for personnel.
- Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
Specification & Design
The 489TB separable connector meets the requirements of CENELEC HD 629,1.
Euromold Type 489TB |
Voltage Um |
Current Ir |
Conductor Size Min-Max |
489TB/G | 12 kV | 1250 Amps | 630-1200 mm2 |
K489TB/G | 24 kV | 1250 Amps | 630-1200 mm2 |
M489TB/G | 36 kV | 1250 Amps | 630-1200 mm2 |
P489TB/G | 42 kV | 1250 Amps | 630-1200 mm2 |
Separable connector comprising:
- Conductive EPDM insert
- Conductive EPDM jacket
- Insulating EPDM layer moulded between the insert and the jacket
- Type C interface as described by CENELEC EN 50180 and 50181
- Conductor contact
- Basic insulating plug (with VD point)
- Cable reducer
- Conductive rubber cap
- Stud & flange nut
- Earthing lead
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
489TB Tee Connector Kit Contents
The complete (K)(M)(P)489TB/G tee connector kit comprises 3 x the following components. The kit also comprises silicone grease, field control mastic, gloves, wipers, roll adhesive tape, installation instructions and crimp chart.
For Ordering Instructions and Part Number Selection Table of Nexans Euromold 489TB Separable Tee Connector (489TB/G, K489TB/G, M489TB/G, P489TB/G), please refer to the Technical Data Table Below. For additional General and Technical Information, download PDF File.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
ORDERING INSTRUCTIONS FOR (K)(M)(P)489TBTo order the tee connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV and a 'P' for use up to 42 kV. Example: The cable is 36 kV, 1000 mm2 stranded aluminium with a diameter over core insulation of 52 mm. Order a 3 x M489TB/G-S-43-1000BI1 tee connector kit. |
PART NUMBER | DIAMETER OVER CORE INSULATION MIN | DIAMETER OVER CORE INSULATION MAX |
3 x 489TB/G-S-37-X | 40 mm | 48 mm |
3 x 489TB/G-S-43-X | 46 mm | 54 mm |
3 x 489TB/G-S-50-X | 53 mm | 59 mm |
3 x 489TB/G-S-53-X | 56 mm | 62 mm |
3 x 489TB/G-S-56-X | 59 mm | 65 mm |
3 x 489TB/G-S-59-X | 62 mm | 68 mm |
TABLE X - ALUMINIUM & COPPER CONDUCTOR |
CONDUCTOR SIZE | Alu Conductor Deep Indent |
Alu & Cu Conductor Bolted |
Cu Conductor DIN Hexagonal |
630 mm2 | 630BI1 | 400.630UN5 | 630CU2 |
800 mm2 | 800BI1 | 800.1000UN5 | 800CU2 |
1000 mm2 | 1000BI1 | 800.1000UN5 | 1000CU2 |
1200 mm2 | 1200BI1 | 1200UN5 | - |