Prysmian BICON A2EX Cable Gland (494AB)
Product overview
Prysmian BICON A2EX Cable Gland (494AB Series) is a brass indoor and outdoor cable gland for use in hazardous locations. Suitable for use with circular unarmoured & braided cables.
Part Numbers: 494AB-51 (A2EX16), 494AB-71 (A2EX20SS), 494AB-52 (A2EX20S), 494AB-53 (A2EX20), 494AB-55 (A2EX25), 494AB-56 (A2EX32), 494AB-57 (A2EX40), 494AB-59 (A2EX50), 494AB-61 (A2EX63), 494AB-62 (A2EX75S), 494AB-63 (A2EX75).
Prysmian 494AB Features
- Brass indoor and outdoor cable gland for use in hazardous areas.
- Suitable for circular Unarmoured cables with extruded oversheath.
- Fitted with silicone rubber low smoke, zero halogen seal.
- Achieves IP66, IP68 (1 bar) and deluge proof (DTS01:1991) seal onto cable and to enclosure with suitable sealing washer or thread sealant.
- Suitable for most climatic conditions – weatherproof, waterproof and deluge proof.
- Standard and Nickel plated versions available.
- Full installation instructions supplied.
- Sizes 32mm and above shall only be used for fixed installations.
- In addition, the user/ installer should ensure that the cables are adequately clamped.
Technical Data
- Certified II 2GD, Ex e II & Ex d IIC under ATEX directive 94/9/EC.
- Atex Compliance Standards: EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1.
- Certificate number Sira99ATEX1086X.
- IECEx Compliance Standards: IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
- Certificate number IECEx SIR 10.0069X.
- Service temperature range -50°C to +200°C.
- UL Classified in accordance with IEC 60079-0, 60079-1 and 60079-7 for use in hazardous locations.
- UL Listed for use in Class 1, Zone 0, 1 and 2 hazardous locations for Canada.
Additional Information
May be used in:
- Zones 0 , 1 & 2 with Ex ia IIA , B & C equipment.
- Zones 1 & 2 with Ex ib IIA , B & C equipment.
- Zones 1 & 2 with Ex e II equipment.
- Zones 1 & 2 with Ex p II equipment.
- Zone 2 with Ex nA II equipment.
- Zones 21 & 22 with Ex tD II equipment.
Where the cable is effectively filled, may also be used in:
- Zones 1 & 2 with Ex d IIC equipment not containing a source of ignition & with a volume less than 2000 cm3.
- Zones 1 & 2 with Ex d IIA & Ex d IIB equipment not containing a source of ignition & with any volume.
- Zone 1 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with a volume less than 2000 cm.
- Zone 2 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with any volume.
- Zone 2 with Ex nR II equipment.
For more information on Prysmian BICON A2EX Cable Gland (494AB Series), please consult Datasheet below.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
Design Reference (Standard) | Design Reference (Nickel Plated) | Size | Cable Diameter Ø (B) mm Min | Cable Diameter Ø (B) mm Max | Entry Thread (D) | Thread Length (E) | Protrusion Length (F) | Hexagon A/F (G) | Hexagon A/C (H) |
494AB-51 | 494AB-51V | 16 | 3.5 | 8.5 | M16 x 1.5 | 15 | 36 | 22 | 24.9 |
494AB-71 | 494AB-71V | 20SS | 3.5 | 8.5 | M20 x 1.5 | 15 | 36 | 22 | 24.9 |
494AB-52 | 494AB-52V | 20S | 8.0 | 11.5 | M20 x 1.5 | 15 | 36 | 22 | 24.9 |
494AB-53 | 494AB-53V | 20 | 8.0 | 16.0 | M20 x 1.5 | 15 | 34 | 25.7 | 28.7 |
494AB-55 | 494AB-55V | 25 | 11.5 | 21.0 | M25 x 1.5 | 15 | 44 | 33 | 36.9 |
494AB-56 | 494AB-56V | 32 | 18.5 | 27.5 | M32 x 1.5 | 15 | 38 | 37.5 | 42.2 |
494AB-57 | 494AB-57V | 40 | 24.0 | 34.0 | M40 x 1.5 | 15 | 46 | 47.2 | 53.6 |
494AB-59 | 494AB-59V | 50 | 31.0 | 41.0 | M50 x 1.5 | 15 | 44 | 56.4 | 61.5 |
494AB-61 | 494AB-61V | 63 | 40.0 | 52.5 | M63 x 1.5 | 15 | 61 | 70 | 77.2 |
494AB-62 | 494AB-62V | 75S | 52.5 | 58.0 | M75 x 1.5 | 15 | 46 | 80 | 87.4 |
494AB-63 | 494AB-63V | 75 | 54.5 | 65.5 | M75 x 1.5 | 15 | 66 | 80 | 87.4 |
Technical Information
- Certified II 2GD, Ex e II & Ex d IIC under ATEX directive 94/9/EC.
- Atex Compliance Standards: EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1.
- Certificate number Sira99ATEX1086X.
- IECEx Compliance Standards: IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
- Certificate number IECEx SIR 10.0069X.
- Service temperature range -50°C to +200°C.
- UL Classified in accordance with IEC 60079-0, 60079-1 and 60079-7 for use in hazardous locations.
- UL Listed for use in Class 1, Zone 0, 1 and 2 hazardous locations for Canada.
Additional Information
May be used in:
- Zones 0 , 1 & 2 with Ex ia IIA , B & C equipment.
- Zones 1 & 2 with Ex ib IIA , B & C equipment.
- Zones 1 & 2 with Ex e II equipment.
- Zones 1 & 2 with Ex p II equipment.
- Zone 2 with Ex nA II equipment.
- Zones 21 & 22 with Ex tD II equipment.
Where the cable is effectively filled, may also be used in:
- Zones 1 & 2 with Ex d IIC equipment not containing a source of ignition & with a volume less than 2000 cm3.
- Zones 1 & 2 with Ex d IIA & Ex d IIB equipment not containing a source of ignition & with any volume.
- Zone 1 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with a volume less than 2000 cm.
- Zone 2 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with any volume.
- Zone 2 with Ex nR II equipment.