Prysmian BICON A2EXP Dual Seal Cable Gland Kit – PVC Shroud (KM495)
Product overview
Prysmian BICON A2EXP Dual Seal Cable Gland Kit – PVC Shroud (KM495 Series) is a brass indoor and outdoor cable gland for use in hazardous locations. Suitable for use with circular unarmoured & braided cables.
Part Numbers: KM495-51, KM495-71, KM495-52, KM495-53, KM495-55, KM495-56, KM495-57, KM495-59, KM495-61, KM495-62, KM495-63.
Prysmian KM495 Features
- Brass indoor and outdoor cable gland for use in hazardous areas.
- Suitable for circular Unarmoured cables with extruded oversheath.
- Fitted with silicone rubber low smoke, zero halogen seal.
- Achieves IP66, IP68 (1 bar) and deluge proof (DTS01:1991) seal onto cable and to enclosure with suitable sealing washer or thread sealant.
- Suitable for most climatic conditions – weatherproof, waterproof and deluge proof.
- Standard and Nickel plated versions available.
- Full installation instructions supplied.
Prysmian KM495 Technical Data
- Certified II 2GD, Ex e II & Ex d IIC under ATEX directive 94/9/EC.
- Atex Compliance Standards: EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1.
- Certificate number Sira99ATEX1086X.
- IECEx Compliance Standards: IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
- Certificate number IECEx SIR 10.0069X.
- Service temperature range -50°C to +200°C.
- UL Classified in accordance with IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
- UL Listed for use in Class 1, Zone 0, 1 and 2 hazardous locations for Canada.
Additional Information
May be used in:
- Zones 0 , 1 & 2 with Ex ia IIA , B & C equipment.
- Zones 1 & 2 with Ex ib IIA , B & C equipment.
- Zones 1 & 2 with Ex e II equipment.
- Zones 1 & 2 with Ex p II equipment.
- Zone 2 with Ex nA II equipment.
- Zones 21 & 22 with Ex tD II equipment.
Where the cable is effectively filled, may also be used in:
- Zones 1 & 2 with Ex d IIC equipment not containing a source of ignition & with a volume less than 2000 cm3.
- Zones 1 & 2 with Ex d IIA & Ex d IIB equipment not containing a source of ignition & with any volume.
- Zone 1 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with a volume less than 2000 cm.
- Zone 2 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with any volume.
- Zone 2 with Ex nR II equipment.
Kit Contents
- A2EX Gland
- Brass Locknut
- Nylon Sealing Washer
- PVC Shroud
- (2 per kit up to and including 25mm size)
For more information on Prysmian BICON A2EXP Dual Seal Cable Gland Kit – PVC Shroud (KM495 Series), please consult Datasheet below.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
Design Reference (Standard) | Design Reference (Nickel Plated) | Size | Qty per Kit | Cable Diameter Ø (B) mm Min | Cable Diameter Ø (B) mm Max | Entry Thread (D) | Thread Length (E) | Protrusion Length (F) | Hexagon A/F (G) | Hexagon A/C (H) |
KM495-51 | KM495-51V | 16 | 2 | 3.5 | 8.5 | M16 x 1.5 | 15 | 65 | 22 | 24.9 |
KM495-71 | KM495-71V | 20SS | 2 | 3.5 | 8.5 | M20 x 1.5 | 15 | 65 | 22 | 24.9 |
KM495-52 | KM495-52V | 20S | 2 | 8.0 | 11.5 | M20 x 1.5 | 15 | 62 | 22 | 24.9 |
KM495-53 | KM495-53V | 20 | 2 | 8.0 | 16.0 | M20 x 1.5 | 15 | 81 | 25.7 | 28.7 |
KM495-55 | KM495-55V | 25 | 2 | 11.5 | 21.0 | M25 x 1.5 | 15 | 85 | 33 | 36.9 |
KM495-56 | KM495-56V | 32 | 1 | 18.5 | 27.5 | M32 x 1.5 | 15 | 69 | 37.5 | 42.2 |
KM495-57 | KM495-57V | 40 | 1 | 24.0 | 34.0 | M40 x 1.5 | 15 | 82 | 47.2 | 53.6 |
KM495-59 | KM495-59V | 50 | 1 | 31.0 | 41.0 | M50 x 1.5 | 15 | 79 | 56.4 | 61.5 |
KM495-61 | KM495-61V | 63 | 1 | 40.0 | 52.5 | M63 x 1.5 | 15 | 113.5 | 70 | 77.2 |
KM495-62 | KM495-62V | 75S | 1 | 52.5 | 58.0 | M75 x 1.5 | 15 | 78.5 | 80 | 87.4 |
KM495-63 | KM495-63V | 75 | 1 | 54.5 | 65.5 | M75 x 1.5 | 15 | 120 | 80 | 87.4 |
Technical Information
- Certified II 2GD, Ex e II & Ex d IIC under ATEX directive 94/9/EC.
- Atex Compliance Standards: EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1.
- Certificate number Sira99ATEX1086X.
- IECEx Compliance Standards: IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
- Certificate number IECEx SIR 10.0069X.
- Service temperature range -50°C to +200°C.
- UL Classified in accordance with IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
- UL Listed for use in Class 1, Zone 0, 1 and 2 hazardous locations for Canada.
Kit Contents
- A2EX Gland
- Brass Locknut
- Nylon Sealing Washer
- PVC Shroud
- (2 per kit up to and including 25mm size)
Additional Information
May be used in:
- Zones 0 , 1 & 2 with Ex ia IIA , B & C equipment.
- Zones 1 & 2 with Ex ib IIA , B & C equipment.
- Zones 1 & 2 with Ex e II equipment.
- Zones 1 & 2 with Ex p II equipment.
- Zone 2 with Ex nA II equipment.
- Zones 21 & 22 with Ex tD II equipment.
Where the cable is effectively filled, may also be used in:
- Zones 1 & 2 with Ex d IIC equipment not containing a source of ignition & with a volume less than 2000 cm3.
- Zones 1 & 2 with Ex d IIA & Ex d IIB equipment not containing a source of ignition & with any volume.
- Zone 1 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with a volume less than 2000 cm.
- Zone 2 with Ex d IIA & Ex d IIB equipment containing a source of ignition & with any volume.
- Zone 2 with Ex nR II equipment.