Prysmian BICON FRZHMPJ & FRZHMB Fire Performance Cable Joints (LV)
Product overview
FRZHMPJ & FRZHMB Cable Joints
Prysmian BICON FRZHMPJ & FRZHMB Fire Performance Cable Joints (LV) are suitable for use with FP400 fire resistant cables.
Part Numbers: FRZHMPJ2, FRZHMPJ3, FRZHMPJ4, FRZHMPJ5, FRZHMPJ6, FRZHMPJ7, FRZHMPJ8, FRZHMB1, FRZHMB2
- To maintain circuit integrity under fire conditions.
- The joint shell material is a fire retardant, rigid thermo setting glass reinforced phenolic which is secured by steel clips.
Prysmian BICON Cable Joints
For many years, BICON has been in the forefront of jointing technology, from designs using bituminous filling compounds, to the development of the highly successful BICAST acrylic resin jointing system.
Most recently, we have supplemented these ranges with heat shrink and pre-moulded products (BIMOLD). We can now offer a unique package to satisfy all requirements.
All four systems are available at voltages up to or above 33 kV and, depending on application, each may offer benefits over the others.
For instance, termination of high voltage polymeric cables requiring the facility to disconnect or add in additional cables at a later stage, means that BIMOLD is the logical choice. Likewise, BICAST provides a fast, comprehensive jointing method with a versatile range covering low and high voltage and all cable types.
Download PDF file for Prysmian BICON Fire Performance Cable Joints (FRZHMPJ3, FRZHMPJ4) Approvals, Features & Benefits and Selection Information.
*Technical Data subject to change without notice.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
FP400 STRAIGHT JOINT - SHELL DIMENSIONS |
Joint Reference | A (mm) | B (mm) | C (mm) |
FRZHMPJ2 | 300 | 85 | 70 |
FRZHMPJ3 | 405 | 100 | 80 |
FRZHMPJ4 | 430 | 110 | 90 |
FRZHMPJ5 | 560 | 160 | 130 |
FRZHMPJ6 | 740 | 180 | 145 |
FRZHMPJ7 | 870 | 190 | 145 |
FRZHMPJ8 | 1015 | 205 | 180 |
LOW VOLTAGE FP400 STRAIGHT JOINTS |
Nominal Conductor Cross Section |
Two Core | Three Core | Four Core | Connector Ref. |
4 mm2 | FRZHMPJ2 | FRZHMPJ2 | FRZHMPJ2 | BE-YS |
6 mm2 | FRZHMPJ2 | FRZHMPJ2 | FRZHMPJ2 | BT6CS |
10 mm2 | FRZHMPJ2 | FRZHMPJ2 | FRZHMPJ2 | BT10CS |
16 mm2 | FRZHMPJ2 | FRZHMPJ3 | FRZHMPJ3 | BT16CS |
25 mm2 | FRZHMPJ2 | FRZHMPJ3 | FRZHMPJ4 | BT25CS |
35 mm2 | FRZHMPJ3 | FRZHMPJ4 | FRZHMPJ4 | BT35CS |
50 mm2 | FRZHMPJ3 | FRZHMPJ5 | FRZHMPJ5 | BT50CS |
70 mm2 | FRZHMPJ4 | FRZHMPJ5 | FRZHMPJ5 | BT70CS |
95 mm2 | FRZHMPJ4 | FRZHMPJ5 | FRZHMPJ5 | BT95CS |
120 mm2 | FRZHMPJ5 | FRZHMPJ6 | FRZHMPJ6 | BT120CS |
150 mm2 | FRZHMPJ5 | FRZHMPJ6 | FRZHMPJ6 | BT150CS |
185 mm2 | FRZHMPJ5 | FRZHMPJ6 | FRZHMPJ6 | BT185CS |
240 mm2 | FRZHMPJ6 | FRZHMPJ7 | FRZHMPJ7 | BT240CS |
300 mm2 | FRZHMPJ6 | FRZHMPJ7 | FRZHMPJ7 | BT300CS |
400 mm2 | - | FRZHMPJ8 | BT400CS |
FP400 BRANCH JOINT - SHELL DIMENSIONS |
Joint Reference | A (mm) | B (mm) | C (mm) |
FRZHMB1 | 300 | 85 | 70 |
FRZHMB2 | 405 | 100 | 80 |
LOW VOLTAGE FP400 BRANCH JOINTS |
Nominal Conductor Cross Section |
Two Core | Three Core | Four Core |
2.5 mm2 | FRZHMB1 | FRZHMB1 | FRZHMB1 |
4 mm2 | FRZHMB1 | FRZHMB1 | FRZHMB1 |
6 mm2 | FRZHMB1 | FRZHMB1 | FRZHMB1 |
10 mm2 | FRZHMB1 | FRZHMB1 | FRZHMB1 |
16 mm2 | FRZHMB1 | FRZHMB1 | FRZHMB2 |
25 mm2 | FRZHMB1 | FRZHMB1 | FRZHMB2 |
35 mm2 | FRZHMB1 | FRZHMB2 | FRZHMB2 |
50 mm2 | FRZHMB2 | FRZHMB2 | FRZHMB2 |
70 mm2 | FRZHMB2 | FRZHMB2 | - |
95 mm2 | FRZHMB2 | FRZHMB2 | - |
120 mm2 | FRZHMB2 | - | - |