Nexans Euromold 200LR Separable Elbow Connector (K200LR-12, K200LR-16)

Product overview

Nexans Euromold 200LR Separable Elbow Connector

Nexans Euromold 200LR Separable Elbow Connector with 250A Current Rating is an elbow connector designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, etc.). Meets the requirements of CENELEC HD 629,1.
Type 200LR Part Numbers: K200LR-12, K200LR-16.

Euromold 200LR is a separable elbow connector specified to terminate and connect medium/high voltage cables onto Interface A bushings in the following voltage classes:

  • 6/10 (12kV)
  • 6.35/11 (12kV)
  • 8.7/15 (17.5kV)
  • 12/20 (24kV)
  • 12.7/22 (24kV)

Technical Characteristics

  • A thick conductive EPDM jacket provides a total safe to touch screen, ensuring personnel safety.
  • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.

Specification & Design

Euromold
Type 200LR
Voltage
Um
Current
Ir
Conductor Size
Min-Max
Diam. Over Insulation
K200LR-12 12 kV
17,5 kV
250 Amps
250 Amps
25-95 mm2
25-50 mm2
13-21 mm
13-21 mm
K200LR-16 17,5 kV
24 kV
250 Amps
250 Amps
50-95 mm2
25-95 mm2
17,5-25 mm
17,5-25 mm

 

Nexans Euromold 200LR DesignSeparable connector comprising:

  1. Conductive EPDM insert.
  2. Conductive EPDM jacket.
  3. Insulating EPDM layer.
  4. Type A interface as described by CENELEC EN 50180 and 50181.
  5. Conductor contact.
  6. Earthing lead.
  7. Cable reducer.

The screen break design enables cable outer sheath testing without removing or dismantling the connector.

200LR Elbow Connector Kit Contents

The complete K200LR elbow connector kit comprises 3 x the following components. The kit also comprises silicon grease, water sealing mastic, gloves, wipers, adhesive tape and installation instructions.

Nexans Euromold 200LR Kit

For Ordering Instructions and Part Number Selection Table of Nexans Euromold 200LR Elbow Connectors (K200LR-12, K200LR-16), please refer to the Technical Data Table Below. For additional General and Technical Information, download PDF File.

FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929

Technical Data

ORDERING INSTRUCTIONS FOR K200LR/G

To order a kit of 3 x elbow connectors, specify the type:

  • for 12 kV applications: 3 x (K200LR-12).
  • for 17.5 kV applications: 3 x (K200LR-12) for 25 up to 50 mm² OR 3 x (K200LR-16) for 50 up to 95 mm².
  • for 24 kV applications: 3 x (K200LR-16).

Example: The cable is 24 kV, 50 mm2 compact stranded aluminium with a diameter over core insulation of 20.5 mm and copper screen wires. Order 3 x (K200LR-16) elbow connector kit.

Additional Options

Voltage Detection Point: A version with a capacitive voltage divider (for voltage detection) and pre-moulded groove (for locking ring installation) is also available. Simply add -VD to the specified type.
Larger Conductor Sizes: A version for larger conductor sizes (120 and 150 mm²) is also available:

PART NUMBER CURRENT (Ir) VOLTAGE (Um)  CONDUCTOR SIZES DIAMETER OVER CORE INSULATION
3 x (K200LR-16-120.150)  250 Amps 12 kV 120 - 150 mm2 17,5 - 25 mm
3 x (K200LR-19-120.150)  250 Amps 17,5-24 kV 120 - 150 mm2 21.5 - 28,5 mm

 

Find out more about our products or becoming a supplier