Nexans Euromold 400T1/ 400AR-1/ 400AR-2 Equipment Bushings

Product overview

Nexans Euromold 400AR-1 Equipment Bushing

Nexans Euromold 400AR-1/ K400AR-1/ M400AR-1 Equipment Bushings are MV-HV Bushings for use in equipment insulated with oil fluid, typically for transformers, switchgear, capacitors that are specified to terminate and connect medium/high voltage cables in the following voltage classes:

  • 6/10 (12kV)
  • 6.35/11 (12kV)
  • 8.7/15 (17.5kV)
  • 12/20 (24kV)
  • 12.7/22 (24kV)
  • 18/30 (36kV)

Technical Characteristics

  • Each bushing is tested for AC withstand and partial discharge prior to leaving the factory.
  • The plug-in type equipment bushings are moulded epoxy insulated parts and meet the requirements of IEC 60137. The (K)(M)400T1 also meets CENELEC EN 50180.

Specification & Design

To order the equipment bushing, specify the type. The bushings can be supplied with an earth jumper (/J) or an earth plate (/GS). This earth connection must be specified when ordering (e.g. K400AR-1/J):

Euromold Equipment
Bushing Type
Voltage
Um
Current
Ir
400AR-1 12 kV 400 Amps
K400AR-1 24 kV 400 Amps
M400AR-1 36 kV 400 Amps

 

Note: For dimensions of the above bushing types, refer to the Technical Data Table below.

Nexans Euromold 400AR-1 Fixings for Bushings

EUROMOLD 400T1 400AR-1 400AR-2 FIXINGS FOR EQUIPMENT BUSHINGS

 

For Ordering Instructions and Part Number Selection Table of Nexans Euromold 400AR-1/ K400AR-1/ M400AR-1 Equipment Bushings, please refer to the Technical Data Table Below. For additional General and Technical Information, download PDF File.

FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929

Technical Data

ORDERING INSTRUCTIONS

To order the equipment bushing, specify the type. The bushings are supplied with an earth jumper (/J) or an earth plate (/GS).

This earth connection must be specified when ordering (e.g. K400AR-1/J).

EQUIPMENT BUSHING TYPE VOLTAGE
Um
CURRENT
Ir
A B C D E Dia. F Dia. G Dia. H
400AR-1 12 kV 400 Amps 380 mm 213 mm 30 mm M12 22 mm 74 mm 128 mm 16 mm
K400AR-1 24 kV 400 Amps 380 mm 213 mm 30 mm M12 22 mm 74 mm 128 mm 16 mm
M400AR-1 36 kV 400 Amps 380 mm 213 mm 30 mm M12 22 mm 74 mm 128 mm 16 mm