Nexans Euromold 809PB Coupling Connector
Product overview
Nexans Euromold 809PB Separable Coupling Connector
Nexans Euromold 809PB Separable Coupling Connector is a coupling connector (bolted type) for dual arrangement. Designed to be used with 480TB, 484TB and 489TB Separable Tee Connectors and meets the requirements of CENELEC HD 629,1. Can also be installed on any 8-series coupling connector for a multiple cable arrangement.
Type 809PB Part Numbers: 809PB/G, K809PB/G, M809PB/G, P809PB/G.
Euromold 809PB is a bolted separable coupling connector specified to terminate and connect medium/high voltage cables in the following voltage classes:
- 6/10 (12kV)
- 6.35/11 (12kV)
- 8.7/15 (17.5kV)
- 12/20 (24kV)
- 12.7/22 (24kV)
- 18/30 (36kV)
- 19/33 (36kV)
- 20.8/36 (42kV)
Technical Characteristics
- A thick conductive EPDM jacket provides a total safe to touch screen which ensures safety for personnel.
- Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
Specification & Design
The 809PB separable connector meets the requirements of CENELEC HD 629,1.
Euromold Type 809PB |
Voltage Um |
Current Ir |
Conductor Size Min-Max |
809PB/G | 12 kV | 1250 Amps | 630-1200 mm2 |
K809PB/G | 24 kV | 1250 Amps | 630-1200 mm2 |
M809PB/G | 36 kV | 1250 Amps | 630-1200 mm2 |
P809PB/G | 42 kV | 1250 Amps | 630-1200 mm2 |
Separable connector comprising:
- Interface designed to fit 480TB, 484TB and 489TB connectors
- Contact rod for 809PB
- Conductor contact
- Conductive EPDM insert
- Conductive EPDM jacket
- Insulating EPDM layer moulded between the insert and the jacket
- Cable reducer
- Conductive EPDM cap
- Basic insulating plug (with VD point)
- Earthing lead
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
809PB Coupling Connector Kit Contents
The complete (K)(M)(P)809PB/G coupling connector kit comprises 3 x the following components. The kit also comprises silicone grease, field control mastic, gloves, wipers, roll adhesive tape, installation instructions and crimp chart.
For Ordering Instructions and Part Number Selection Table of Nexans Euromold 809PB Separable Coupling Connector (809PB/G, K809PB/G, M809PB/G, P809PB/G), please refer to the Technical Data Table Below. For additional General and Technical Information, download PDF File.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
ORDERING INSTRUCTIONS FOR (K)(M)(P)809PBTo order the coupling connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV and a 'P' for use up to 42 kV. Example: The copper wire screened cable is 36 kV, 1000 mm2 stranded aluminium with a diameter over core insulation of 52 mm. Order 3 x M809PB/G-S-43-1000BI1 coupling connector kit. |
PART NUMBER | DIAMETER OVER CORE INSULATION MIN | DIAMETER OVER CORE INSULATION MAX |
3 x 809PB/G-S-37-X | 40 mm | 48 mm |
3 x 809PB/G-S-43-X | 46 mm | 54 mm |
3 x 809PB/G-S-50-X | 53 mm | 59 mm |
3 x 809PB/G-S-53-X | 56 mm | 62 mm |
3 x 809PB/G-S-56-X | 59 mm | 65 mm |
3 x 809PB/G-S-59-X | 62 mm | 68 mm |
TABLE X - CONNECTORS SUITABLE FOR COPPER & ALUMINIUM CABLES |
CONDUCTOR SIZE | Alu Conductor Deep Indent |
Alu & Cu Conductor Bolted |
Cu Conductor DIN Hexagonal |
630 mm2 | 630BI1 | 400.630UN5 | 630CU2 |
800 mm2 | 800BI1 | 800.1000UN5 | 8300CU2 |
1000 mm2 | 1000BI1 | 800.1000UN5 | 10400CU2 |
1200 mm2 | 1200BI1 | 1200UN5 | - |