Nexans Euromold 909PB Coupling Connector (909PB/G, K909PB/G, M909PB/G, P909PB/G)

Product overview

Nexans Euromold 909PB Separable Coupling Connector

Nexans Euromold 909PB Separable Coupling Connector is a coupling connector (bolted type) for dual arrangement. Designed to be used with 909TB Separable Tee Connectors and meets the requirements of CENELEC HD 629,1.
Type 909PB Part Numbers: 909PB/G, K909PB/G, M909PB/G, P909PB/G.

Euromold 909PB is a bolted separable coupling connector specified to terminate and connect medium/high voltage cables in the following voltage classes:

  • 6/10 (12kV)
  • 6.35/11 (12kV)
  • 8.7/15 (17.5kV)
  • 12/20 (24kV)
  • 12.7/22 (24kV)
  • 18/30 (36kV)
  • 19/33 (36kV)
  • 20.8/36 (42kV)

Technical Characteristics

  • The thick conductive EPDM jacket provides a total safe to touch screen which ensures safety for personnel.
  • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.

Specification & Design

The 909PB separable connector meets the requirements of CENELEC HD 629,1.

Euromold
Type 909PB
Voltage
Um
Current
Ir
Conductor Size
Min-Max
909PB/G 12 kV 630-1250-2500 Amps 500-1200 mm2
K909PB/G 24 kV 630-1250-2500 Amps 400-1200 mm2
M909PB/G 36 kV 630-1250-2500 Amps 240-1200 mm2
P909PB/G 42 kV 630-1250Amps 240-1200 mm2

 

Nexans Euromold 909PB DesignSeparable connector comprising:

  1. Conductive EPDM insert
  2. Conductive EPDM jacket
  3. Insulating EPDM layer moulded between the insert and the jacket
  4. Interface to fit 909TB
  5. Conductor contact
  6. Basic insulating plug
  7. Cable reducer
  8. Conductive rubber cap
  9. Stud + nut + washer
  10. Earthing lead

The screen break design enables cable outer sheath testing without removing or dismantling the connector.

909PB Coupling Connector Kit Contents

The complete (K)(M)(P)909PB/G connector kit comprises the following components. The kit also comprises silicone grease, field control mastic, gloves, roll adhesive tape, installation instructions and crimp chart.

Nexans Euromold 909PB Kit

For Ordering Instructions and Part Number Selection Table of Nexans Euromold 909PB Separable Coupling Connector (909PB/G, K909PB/G, M909PB/G, P909PB/G), please refer to the Technical Data Table Below. For additional General and Technical Information, download PDF File.

FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929

Technical Data

ORDERING INSTRUCTIONS FOR (K)(M)(P)909PB

To order the coupling connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV and a 'P' for use up to 42 kV.

Example: The cable is 36 kV, 1000 mm2 stranded aluminium with a diameter over core insulation of 52 mm. Order M909PB/G-S-43-1000AL1 connector kit.

PART NUMBER DIAMETER OVER CORE INSULATION MIN DIAMETER OVER CORE INSULATION MAX
909PB/G-S-32-X 35 mm 43 mm
909PB/G-S-37-X 40 mm 48 mm
909PB/G-S-43-X 46 mm 54 mm
909PB/G-S-50-X 53 mm 59 mm
909PB/G-S-53-X 56 mm 62 mm
909PB/G-S-56-X 59 mm 65 mm
909PB/G-S-59-X 62 mm 68 mm

 

TABLE X - ALUMINIUM & COPPER CONDUCTOR

CONDUCTOR SIZE  Alu Conductor
DIN Hexagonal
Alu Conductor
Deep Indent
Alu & Cu Conductor
Bolted
Cu Conductor
DIN Hexagonal
240 mm2 240BI2 240BI1 240.300UN5 240CU2
300 mm2 300BI2 300BI1 240.300UN5 300CU2
400 mm2 400BI2 400BI1 400.630UN5 400CU2
500 mm2 500BI2 500BI1 400.630UN5 500CU2
630 mm2 630BI2 630BI1 400.630UN5 630CU2
800 mm2 - 800BI1 800.1000UN5 800CU2
1000 mm2 - 1000BI1 800.1000UN5 1000CU2
1200 mm2 - 1200BI1 On Request -

 