Prysmian BICON Barr-A Exd IIC Cable Gland (424TA)
Product overview
Prysmian BICON Barr-A Exd IIC Cable Gland (424TA Series) is a brass indoor and outdoor cable gland for use in Zone 1 and Zone 2 hazardous areas. Suitable for use with circular unarmoured cables.
Part Numbers: 424TA-53, 424TA-55, 424TA-56, 424TA-57, 424TA-59, 424TA-61, 424TA-63, 424TA-64, 424TA-03, 424TA-05, 424TA-06, 424TA-07, 424TA-09, 424TA-11, 424TA-13, 424TA-14.
Prysmian 424TA Features
- Brass indoor and outdoor cable gland for use in Zone 1 and Zone 2 hazardous areas.
- Suitable for circular unarmoured cables with extruded oversheath.
- Achieves IP66 seal onto cable and to enclosure with suitable sealing washer or thread sealant.
- Provides mechanical cable retention.
- Suitable for most climatic conditions – weatherproof and waterproof.
- Standard and Nickel plated versions available.
- Full Installation Instructions supplied.
- *Other NPT sizes available upon request.
Technical Data
- Certified II 2GD, Ex e II & Ex d IIC under ATEX directive 94/9/EC.
- Atex Compliance Standards: EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1.
- Certificate number Sira04ATEX1080X.
- IECEx Compliance Standards: IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
- Certificate number IECEx SIR 10.0072X
- Service temperature range -60°C to +90°C.
Additional Information
May be used in:
- Zones 0 , 1 & 2 with Ex ia IIA , B & C equipment.
- Zones 1 & 2 with Ex ib IIA , B & C equipment.
- Zones 1 & 2 with Ex ib IIA , B & C equipment with any volume.
- Zones 1 & 2 with Ex e II equipment.
- Zones 1 & 2 with Ex p II equipment.
- Zone 2 with Ex nA II equipment.
- Zone 2 with Ex nR II equipment.
- Zones 21 & 22 with Ex tD A21.
For more information on Prysmian BICON Barr-A Exd IIC Cable Gland (424TA Series), please consult Datasheet below.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
Design Reference (Standard) | Design Reference (Nickel Plated) | Size (Metric) | Size (NPT) | Max. Dia. Over Conductors | Max. No. Over Conductors | Overall Ø (B) Min | Overall Ø (B) Max | Entry Thread (D) | Thread Length (E) | Protrusion Length (F) | Hexagon A/F (G) | Hexagon A/C (H) |
424TA-53 | 424TA-53V | 20 | 11.0 | 30 | 8.9 | 15.7 | M20 x 1.5 | 15 | 56 | 36 | 40 | |
424TA-55 | 424TA-55V | 25 | 16.0 | 42 | 13.0 | 19.3 | M25 x 1.5 | 15 | 59 | 42.4 | 48 | |
424TA-56 | 424TA-56V | 32 | 22.1 | 60 | 17.0 | 25.4 | M32 x 1.5 | 15 | 59 | 47.2 | 53.6 | |
424TA-57 | 424TA-57V | 40 | 28.2 | 100 | 24.1 | 30.0 | M40 x 1.5 | 15 | 63 | 56.4 | 61.5 | |
424TA-59 | 424TA-59V | 50 | 37.1 | 200 | 29.0 | 41.9 | M50 x 1.5 | 15 | 66 | 70.1 | 77.2 | |
424TA-61 | 424TA-61V | 63 | 48.4 | 400 | 40.9 | 52.8 | M63 x 1.5 | 15 | 69 | 80 | 87.4 | |
424TA-63 | 424TA-63V | 75 | 58.6 | 400 | 49.8 | 59.9 | M75 x 1.5 | 15 | 80 | 98.8 | 109.2 | |
424TA-64 | 424TA-64V | 85 | 65.8 | 400 | 58.9 | 73.9 | M85 x 2 | 20 | 83 | 106.2 | 116.8 | |
424TA-03 | 424TA-03V | ½"-20 | 11.0 | 30 | 8.9 | 15.7 | ½" NPT | 21.9 | 56 | 36 | 40 | |
424TA-05 | 424TA-05V | ¾"-25 | 16.0 | 42 | 13.0 | 19.3 | ¾" NPT | 22.2 | 59 | 42.4 | 48 | |
424TA-06 | 424TA-06V | 1"-32 | 22.1 | 60 | 17.0 | 25.4 | 1" NPT | 27.5 | 59 | 47.2 | 53.6 | |
424TA-07 | 424TA-07V | 1¼"-40 | 28.2 | 100 | 24.1 | 30.0 | 1¼" NPT | 28.1 | 63 | 56.4 | 61.5 | |
424TA-09 | 424TA-09V | 2"-50 | 37.1 | 200 | 29.0 | 41.9 | 2" NPT | 29.4 | 66 | 70.1 | 77.2 | |
424TA-11 | 424TA-11V | 2½"-63 | 48.4 | 400 | 40.9 | 52.8 | 2½" NPT | 43.4 | 69 | 80 | 87.4 | |
424TA-13 | 424TA-13V | 3"-75 | 58.6 | 400 | 49.8 | 59.9 | 3" NPT | 45.0 | 80 | 98.8 | 109.2 | |
424TA-14 | 424TA-14V | 3"-85 | 65.8 | 400 | 58.9 | 73.9 | 3" NPT | 45.0 | 83 | 106.2 | 116.8 |
Technical Information
- Certified II 2GD, Ex e II & Ex d IIC under ATEX directive 94/9/EC.
- Atex Compliance Standards: EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1.
- Certificate number Sira04ATEX1080X.
- IECEx Compliance Standards: IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
- Certificate number IECEx SIR 10.0072X
- Service temperature range -60°C to +90°C.
Additional Information
May be used in:
- Zones 0 , 1 & 2 with Ex ia IIA , B & C equipment.
- Zones 1 & 2 with Ex ib IIA , B & C equipment.
- Zones 1 & 2 with Ex ib IIA , B & C equipment with any volume.
- Zones 1 & 2 with Ex e II equipment.
- Zones 1 & 2 with Ex p II equipment.
- Zone 2 with Ex nA II equipment.
- Zone 2 with Ex nR II equipment.
- Zones 21 & 22 with Ex tD A21.