Prysmian BICON Barr-X Exd IIC Cable Gland (424TX)
Product overview
Prysmian BICON Barr-X Exd IIC Cable Gland (424TX Series) is a brass indoor and outdoor cable gland for use in Zone 1 and Zone 2 hazardous areas. Suitable for use with braid armoured cables.
Part Numbers: 424TX- 52, 424TX-53, 424TX-55, 424TX-56, 424TX-57, 424TX-59, 424TX-61, 424TX-63, 424TX-64, 424TX-02, 424TX-03, 424TX-05, 424TX-06, 424TX-07, 424TX-09, 424TX-11, 424TX-13, 424TX-14.
Prysmian 424TX Features
- Brass indoor and outdoor cable gland for use in Zone 1 and Zone 2 hazardous areas.
- Suitable for circular, wire braid armour cables with extruded polymeric oversheath and extruded or taped bedding.
- Achieves IP66 seal onto cable and to enclosure with suitable sealing washer or thread sealant.
- Provides mechanical cable retention and electrical continuity through the braid wire termination.
- Suitable for most climatic conditions – weatherproof and waterproof.
- Standard and Nickel plated versions available.
- Full Installation Instructions supplied.
- *Other NPT sizes available upon request.
Technical Data
- Certified II 2GD, Ex e II & Ex d IIC under ATEX directive 94/9/EC.
- Atex Compliance Standards: EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1.
- Certificate number Sira04ATEX1080X.
- IECEx Compliance Standards: IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
- Certificate number IECEx SIR 10.0072X
- Service temperature range -60°C to +90°C.
Additional Information
May be used in:
- Zones 0 , 1 & 2 with Ex ia IIA , B & C equipment.
- Zones 1 & 2 with Ex ib IIA , B & C equipment.
- Zones 1 & 2 with Ex ib IIA , B & C equipment with any volume.
- Zones 1 & 2 with Ex e II equipment.
- Zones 1 & 2 with Ex p II equipment.
- Zone 2 with Ex nA II equipment.
- Zone 2 with Ex nR II equipment.
- Zones 21 & 22 with Ex tD A21.
For more information on Prysmian BICON Barr-X Exd IIC Cable Gland (424TX Series), please consult Datasheet below.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
Design Reference (Standard) | Design Reference (Nickel Plated) | Size (Metric) | Size (NPT) | Max. Dia. Over Conductors | Max. No. Over Conductors | Inner Sheath Min Ø | Inner Sheath Max Ø | Overall Ø (B) Min | Overall Ø (B) Max | Braid Armour Wire Ø | Entry Thread (D) | Thread Length (E) | Protrusion Length (F) | Hexagon A/F (G) | Hexagon A/C (H) |
424TX- 52 | 424TX-52V | 20S | - | 11.0 | 30 | - | 11.5 | 8.0 | 15.8 | 0.2/0.3 | M20 x 1.5 | 15 | 67 | 30.5 | 34 |
424TX-53 | 424TX-53V | 20 | - | 11.0 | 30 | - | 12.5 | 11.7 | 20.8 | 0.2/0.3 | M20 x 1.5 | 15 | 64 | 30.5 | 34 |
424TX-55 | 424TX-55V | 25 | - | 16.0 | 42 | 11.5 | 18.0 | 17.0 | 27.2 | 0.2/0.45 | M25 x 1.5 | 15 | 65 | 37.6 | 42.2 |
424TX-56 | 424TX-56V | 32 | - | 22.1 | 60 | 17.0 | 25.0 | 19.0 | 33.5 | 0.3/0.45 | M32 x 1.5 | 15 | 77 | 47.3 | 53.6 |
424TX-57 | 424TX-57V | 40 | - | 28.2 | 100 | 24.0 | 31.5 | 26.5 | 39.9 | 0.3/0.45 | M40 x 1.5 | 15 | 77 | 56.4 | 61.5 |
424TX-59 | 424TX-59V | 50 | - | 37.1 | 200 | 30.0 | 41.5 | 36.0 | 52.6 | 0.3/0.45 | M50 x 1.5 | 15 | 84 | 70.1 | 77.2 |
424TX-61 | 424TX-61V | 63 | - | 48.4 | 400 | 40.0 | 54.0 | 46.5 | 65.3 | 0.3/0.45 | M63 x 1.5 | 15 | 90 | 80 | 87.4 |
424TX-63 | 424TX-63V | 75 | - | 58.6 | 400 | 53.0 | 65.5 | 58.0 | 78.0 | 0.3/0.45 | M75 x 1.5 | 15 | 96 | 98.8 | 109.2 |
424TX-64 | 424TX-64V | 85 | - | 65.8 | 400 | 60.0 | 74.0 | 68.0 | 88.0 | 0.3/0.45 | M85 x 2 | 20 | 108 | 115 | 126 |
424TX-02 | 424TX-02V | - | ½"-20S | 11.0 | 30 | - | 11.5 | 8.0 | 15.8 | 0.2/0.3 | ½" NPT | 21.9 | 67 | 30.5 | 34 |
424TX-03 | 424TX-03V | - | ½"-20 | 11.0 | 30 | - | 12.5 | 11.7 | 20.8 | 0.2/0.3 | ½" NPT | 21.9 | 64 | 30.5 | 34 |
424TX-05 | 424TX-05V | - | ¾"-25 | 16.0 | 42 | 11.5 | 18.0 | 17.0 | 27.2 | 0.2/0.45 | ¾" NPT | 22.2 | 65 | 37.6 | 42.2 |
424TX-06 | 424TX-06V | - | 1"-32 | 22.1 | 60 | 17.0 | 25.0 | 19.0 | 33.5 | 0.3/0.45 | 1" NPT | 27.5 | 77 | 47.3 | 53.6 |
424TX-07 | 424TX-07V | - | 1¼"-40 | 28.2 | 100 | 24.0 | 31.5 | 26.5 | 39.9 | 0.3/0.45 | 1¼" NPT | 28.1 | 77 | 56.4 | 61.5 |
424TX-09 | 424TX-09V | - | 2"-50 | 37.1 | 200 | 30.0 | 41.5 | 36.0 | 52.6 | 0.3/0.45 | 2" NPT | 29.4 | 84 | 70.1 | 77.2 |
424TX-11 | 424TX-11V | - | 2½"-63 | 48.4 | 400 | 40.0 | 54.0 | 46.5 | 65.3 | 0.3/0.45 | 2½" NPT | 43.4 | 90 | 80 | 87.4 |
424TX-13 | 424TX-13V | - | 3"-75 | 58.6 | 400 | 53.0 | 65.5 | 58.0 | 78.0 | 0.3/0.45 | 3" NPT | 45.0 | 96 | 98.8 | 109.2 |
424TX-14 | 424TX-14V | - | 3"-85 | 65.8 | 400 | 60.0 | 74.0 | 68.0 | 88.0 | 0.3/0.45 | 3" NPT | 45.0 | 108 | 115 | 126 |
Technical Information
- Certified II 2GD, Ex e II & Ex d IIC under ATEX directive 94/9/EC.
- Atex Compliance Standards: EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1.
- Certificate number Sira04ATEX1080X.
- IECEx Compliance Standards: IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
- Certificate number IECEx SIR 10.0072X
- Service temperature range -60°C to +90°C.
Additional Information
May be used in:
- Zones 0 , 1 & 2 with Ex ia IIA , B & C equipment.
- Zones 1 & 2 with Ex ib IIA , B & C equipment.
- Zones 1 & 2 with Ex ib IIA , B & C equipment with any volume.
- Zones 1 & 2 with Ex e II equipment.
- Zones 1 & 2 with Ex p II equipment.
- Zone 2 with Ex nA II equipment.
- Zone 2 with Ex nR II equipment.
- Zones 21 & 22 with Ex tD A21.