Nexans-Euromold-400TR-400TR-LB-Interface-C-Test-Rods

Product overview

Nexans Euromold 400TR Test Rod

Nexans Euromold 400TR Test Rod can be used for cable fault location, cable testing, phase check, etc. You can make connections using a cable lug, a 4 mm plug or spring clips. The 400TR test rod works with 400TE, 400TB and 440TB connectors.

400TR Test Rod Specification & Design

Simply specify: 400TR Test Rod

Test Rod 
Type
Max AC
Test Voltage

(50Hz – 1min)
Max DC
Test Voltage

(8xU0 – 30min)
Impulse Voltage
(1.2 x 50 μs) min
400TR 36 kV 96 kV 95 kV

 

Euromold-400TR-800TR-Test-Rod-11kV-33kV-1Separable connector comprising:

  1. Insulating Shroud
  2. Threaded rod for test connection
  3. Two M12 nuts
  4. Insulation
  5. Copper test rod stem
  6. Wing nut

An insulating shroud is provided to allow the application of test voltages when bushings are closely spaced.

Installation

You mount the test rod onto the clamping screw in the type C interface tee and coupling connectors. Then, connect the test cable to the threaded stem and move the insulating shroud to its final position over the end of the test rod.

For additional General and Technical Information, download PDF File.

FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929

Technical Data

Test Rod Type Max AC Test Voltage (50Hz - 1min) Max DC Test Voltage (8xU0 - 30min) Impulse Voltage (1.2 x 50 μs) min
400TR 36 kV 96 kV 95 kV

Find out more about our products or becoming a supplier