Nexans Euromold 800SA-58 Surge Arrester
Product overview
Nexans Euromold 800SA-58 Surge Arrester
Nexans Euromold 800SA-58 Surge Arrester is designed to protect 12kV, 24kV, 36kV and 42kV components, including transformers, equipment, cable and accessories from high voltage surges resulting from lightning or switching. Designed to be used with the 784TB separable tee connectors (Aluminium & Copper). Meets the test requirements of IEC 60099-4.
Euromold 800SA-58 used for medium/high voltage cables in the following voltage classes:
- 6/10 (12kV)
- 6.35/11 (12kV)
- 8.7/15 (17.5kV)
- 12/20 (24kV)
- 12.7/22 (24kV)
- 18/30 (36kV)
- 19/33 (36kV)
- 20.8/36 (42kV)
Technical Characteristics
- This surge arrester is a metal oxide varistor surge arrester in an elbow configuration.
- Each arrester is tested for AC withstand, partial discharge and critical voltage prior to leaving the factory.
Specification & Design
The 800SA-58 separable connector meets the requirements of IEC 60099-4.
Euromold Surge Arrester Type |
Nominal Discharge Current In |
Rated Voltage Ur |
Max Continuous Operating Voltage Uc |
Dim. L1-L2 (mm) |
800SA-58-10-6N | 10 kA | 6 kV | 4.8 kV | 270-310 |
800SA-58-10-9N | 10 kA | 9 kV | 7.2 kV | 270-310 |
800SA-58-10-12N | 10 kA | 12 kV | 9.6 kV | 270-310 |
800SA-58-10-15N | 10 kA | 15 kV | 12 kV | 270-310 |
800SA-58-10-18N | 10 kA | 18 kV | 14.4 kV | 270-310 |
800SA-58-10-22N | 10 kA | 22 kV | 17.6 kV | 270-310 |
800SA-58-10-24N | 10 kA | 24 kV | 19.2 kV | 370-410 |
800SA-58-10-30N | 10 kA | 30 kV | 24 kV | 370-410 |
800SA-58-10-33N | 10 kA | 33 kV | 26.4 kV | 370-410 |
800SA-58-10-36N | 10 kA | 36 kV | 28.8 kV | 370-410 |
800SA-58-10-45N | 10 kA | 45 kV | 36 kV | 470-510 |
800SA-58-10-51N | 10 kA | 51 kV | 40.8 kV | 470-510 |
- Interface designed to fit the 784TB tee connector (Aluminium & Copper)
- Conductive EPDM insert
- Conductive EPDM jacket
- Insulating EPDM layer moulded between the insert and the jacket
- Receptacle for contact rod
- Metal oxide valve elements
- Steel cap
- Earth connection
- Earthing lead
For Ordering Instructions and Part Number Selection Table of Nexans Euromold 800SA-58 Surge Arrester, please refer to the Technical Data Table Below. For additional General and Technical Information, download PDF File.
FREE Technical Advisory Service
E-Tech Components UK Ltd maintains a free technical advisory service.
Contact us for enquiries concerning this and all other products: +44 (0) 1744 762 929
Interested in this Product?
+44 (0)1744 762 929Technical Data
ORDERING INSTRUCTIONS FOR 800SA-58To order the surge arrester, specify the surge arrester type, as described above. Example: For a maximum continuous operating voltage (r.m.s.) of 24 kV and a nominal discharge current of 10 kA, order an 800SA-58-10-30N surge arrester. |
Surge Arrester Type |
Steep Current Residual Voltage 10kA [1/20μs] |
Lightning Current Residual Voltage 5kA [8/20μs] |
Lightning Current Residual Voltage 10kA [8/20μs] |
Lightning Current Residual Voltage 20kA [8/20μs] |
Switching Impulse Residual Voltage 125A [36/90μs] |
Switching Impulse Residual Voltage 500A [36/90μs] |
High Current Impulse Withstand |
800SA-58-10-6N | 20.4 | 16.8 | 18.3 | 20.5 | 12.9 | 13.7 | 100 kA |
800SA-58-10-9N | 28.5 | 23.5 | 25.6 | 28.7 | 18 | 19.2 | 100 kA |
800SA-58-10-12N | 38 | 31.4 | 34.2 | 38.3 | 24.1 | 25.7 | 100 kA |
800SA-58-10-15N | 48.1 | 39.7 | 43.2 | 48.4 | 30.5 | 32.5 | 100 kA |
800SA-58-10-18N | 58.1 | 48 | 52.2 | 58.5 | 36.8 | 39.2 | 100 kA |
800SA-58-10-22N | 70.1 | 57.9 | 63 | 70.6 | 44.4 | 47.3 | 100 kA |
800SA-58-10-24N | 77 | 63.6 | 69.2 | 77.6 | 48.8 | 52 | 100 kA |
800SA-58-10-30N | 97 | 80.1 | 87.2 | 97.7 | 61.5 | 65.5 | 100 kA |
800SA-58-10-33N | 103.4 | 85.4 | 93 | 104.2 | 65.6 | 69.9 | 100 kA |
800SA-58-10-36N | 115.9 | 95.7 | 104.2 | 116.8 | 73.5 | 78.3 | 100 kA |
800SA-58-10-45N | 144.1 | 119 | 129.5 | 145.1 | 91.3 | 97.3 | 100 kA |
800SA-58-10-51N | 166 | 137.1 | 149.2 | 167.2 | 105.2 | 112.1 | 100 kA |